| 2009-08-19 15:21:40 | |
| | |
| | ** DENIED REVIEW ** |
| | |
| | 1) NOTE: PLEASE PROVIDE MINIMUM CLEARANCES FOR |
| | GENERATOR PER 110.26. THE PLANS INDICATE 2FT 6INCHES. |
| | PLEASE ALSO CHECK WITH THE MANUFACTURE AS THERE ARE |
| | MINIMUM CLEARANCE REQUIREMENTS ALSO FOR VENTILATION. |
| | 110.3,90.7 ETC |
| | |
| | 2) NOTE: MAY NOT SUBMIT PLANS DONE BY AN ENGINEER FOR |
| | PERMITTING AND RECORD PLANS UNLESS SIGNED, DATED AND |
| | SEALED BY SAID ENGINEER. |
| | FS 471.025 |
| | FAC61G15-23.002 |
| | |
| | 3) NOTE: PLEASE BE SURE TITLE BLOCK INCLUDES THE |
| | CERTIFICATE OF AUTHORIZATION NUMBER FOR ARCHITECTURAL |
| | FIRM. FS 481.221, FAC 61G1-16.004 |
| | |
| | 4) NOTE: PLEASE SEE PLANS ARE NOTING DESIGN PER 2004 |
| | FBC, ASCE-7-02, 90MPH, EXPOSURE *C*. |
| | PLEASE CHECK DESIGN. |
| | THE WIND ZONE IN THE CITY OF WEST PALM BEACH IS 140MPH, |
| | 3SEC GUST. |
| | PLEASE ALSO KNOW AS OF MARCH 1ST, 2009 THE STATE OF |
| | FLORIDA ADOPTED THE 2007 FBC WITH THE 2009 GLITCH |
| | AMENDMENTS. |
| | PLEASE KNOW THAT THERE WERE CHANGES IN EXPOSURE |
| | CATEGORIES. |
| | THIS JURISDICTION IS NOT REVIEWING FOR DESIGN OF FENCE |
| | MEETING MINIMUM CODE HOWEVER PLANS SUBMITTED FOR |
| | PERMITTING ARE REQUIRED TO CONTAIN CORRECT CODES. |
| | PLEASE BE SURE TO VERIFY FOR PUBLIX CORPORATE OFFICES |
| | FOR MINIMUM DESIGNS. |
| | |
| | 5) NOTE: PLEASE BE SURE TO COORDINATE PLANS. ELECTRICAL |
| | SHEETS STATE 10FT 6INCHES ON FENCE AND SHEET PVC5 |
| | STATES 10FT. |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |