| Plan Review Notes For Permit 09080125 |
| Permit Number |
09080125 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-08-17 13:33:03 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2005 | | | NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} THE SQUARE FOOTAGE AND LIGHTING POWER COMPLIANCE IN | | | THE FLA/COM AND THE LIGHTING PERFORMANCE CALCULATIONS | | | ON SHEET E-1.1DO NOT CORRELATE. 13-415,AB,5. THE DESIGN | | | WATTS ARE OVER THE ALLOWABLE WATTS IN THE LIGHTING | | | PERFORMANCE CALCULATION, SHEET E-1.1. | | | | | | 2} 240.24(D) NOT IN VICINITY OF EASILY IGNITIBLE | | | MATERIAL OVERCURRENT DEVICES SHALL NOT BE LOCATED IN | | | THE VICINITY OF EASILY IGNITIBLE MATERIAL, SUCH AS IN | | | CLOTHES CLOSETS. | | | EXAMPLES OF LOCATIONS WHERE COMBUSTIBLE MATERIALS MAY | | | BE STORED ARE LINEN CLOSETS, PAPER STORAGE CLOSETS, AND | | | CLOTHES CLOSETS.INDICATE WHAT MATERIALS ARE INTENDED TO | | | BE STORED IN ROOM 105. ALSO SEE 110.26. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|