| 2009-08-19 19:34:36 | |
| | |
| | |
| | |
| | |
| | |
| | ** DENIED REVIEW ** |
| | |
| | ** PLANS ARE MISSING INFORMATION NOT YET SHOWN. THERE |
| | ARE SEVERAL ITEMS WHICH CAN NOT BE REVIEWED FOR MINIMUM |
| | CODE COMPLIANCE AT THIS TIME. THERE MAY VERY WELL BE |
| | NEW COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT |
| | POSSIBLY BE MADE AT THIS TIME> SEE NOTES. |
| | |
| | 1) NOTE: PLEASE SEE THAT SOME OF THE CODE INFORMATION |
| | FOR MINIMUM DESIGNS LISTED ON COVER SHEET IS NOT |
| | CORRECT. |
| | PLANS INDICATE 2004 FBC FOR CHAPTER 11. HOWEVER AS OF |
| | MARCH 1ST, 2009 THE STATE OF FLORIDA ADOPTED THE 2007 |
| | FBC W/ 2009 SUPPLEMENTS. THIS INCLUDES CHAPTER 11 UNDER |
| | THE 2007 FBC. |
| | THE PLANS STATE THE 2004 FLORIDA FIRE PREVENTION CODE |
| | HOWEVER AS OF DECEMBER 31ST, 2008 THE STATE ADOPTED THE |
| | 2007 FFPC. PLEASE SEE FLORIDA ADMINISTRATIVE CODE |
| | 69A-60 |
| | PLEASE ALSO SEE THE SECTIONS 69A-60.003 AND .004 AS THE |
| | FOLLOWING NFPA-1 AND NFPA-101 ( LIFE SAFETY CODE ) IS |
| | ACTUALLY THE 2006 EDITIONS. PLANS STATE THE 2003 |
| | EDITION OF NFPA-101. |
| | |
| | ** LIGHTING CONTROLS STATES TO MEET THE FBC WITH 2006 |
| | SUPPLEMENTS. AS NOTED ABOVE THE 2006 SUPPLEMENTS WOULD |
| | BE UNDER THE 2004 FBC. NOT THE CURRENT 2007 FBC WITH |
| | 2009 SUPPLEMENTS. |
| | |
| | 2) NOTE: PLEASE PROVIDE SIGNED CONTRACTS OR ADJUST |
| | VALUE FOR COMPLETE SCOPE OF WORK AS THE APPLIED VALUE |
| | IS LOW. THE APPLIED VALUE SHALL INCLUDE ALL LABOR, |
| | MATERIALS, PERMANENTLY INSTALLED EQUIPMENT, DESIGN COST |
| | ETC EVEN IF ANY OF THESE ITEMS ARE OWNER SUPPLIED. |
| | FBC 108.3 |
| | THE APPLIED VALUE OF $200K FOR THE ENTIRE PROJECT IS |
| | LOW. |
| | |
| | 3) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE |
| | CALCULATIONS FOR NEW BEING INSTALLED ALONG WITH |
| | EXISTING. PLEASE SEE 13-415.AB.5, 13-415.B. THE |
| | SUBMITTED SINGLE FORM B IS NOT ACCEPTABLE FOR SCOPE OF |
| | WORK AS SHOWN. FORM 400B IS PERMITTED HOWEVER THIS |
| | WOULD REQUIRE THIS SAME FOR EACH AND EVERY SPACE IN THE |
| | TENANT SPACE. |
| | PLEASE SEE 13-400.0.B.4 WHEN NOT MEETING THE DEFINITION |
| | OF *RENOVATION* OF A BUILDING THEN ALL NEW INSTALLED |
| | MUST MEET PRESCRIPTIVE REQUIREMENTS. SEE SECTIONS NOTED |
| | AND SEE SECTION 202 FOR DEFINITIONS. |
| | THE SUBMITTED INFORMATION ON PLANS IS OVER THE LIGHTING |
| | ALLOWANCES PERMITTED. PLEASE KNOW THE SPACE BY SPACE IS |
| | JUST THAT. SPACE BY SPACE ALLOWANCES MAY NOT USE FAMILY |
| | DINING ALLOWANCES FOR THE BATHROOMS, STORAGE ROOMS, |
| | ETC. THE BAR LOUNGE ALLOWANCES MAY NOT BE USED FOR THE |
| | OTHER TYPES OF AREAS. ALL SEPARATE SPACE MUST BE |
| | DESIGNATED. |
| | PLEASE ALSO KNOW THAT THAT LIGHTING ALLOWANCE WATTAGE |
| | SHOWN ON LIGHTING CONTROL PANELS ON SHEET E-5.0 IS |
| | HIGHER THAN THE DESIGN ON SHEET E-4.0. |
| | PLEASE KNOW AT THIS TIME DESIGN IS SUBSTANTIALLY OVER |
| | THE MAXIMUM ALLOWANCES PERMITTED BY THE ENERGY CODE. |
| | THIS IS BASED ON THE INFORMATION STATED AND SHOWN ON |
| | PLANS. |
| | ** FIXTURE WATTAGES ARE NOT BASED ON LIGHT BULBS, IT |
| | MUST BE FIGURED PER FIXTURE. * FIXTURE O FOR ONLY ONE |
| | EXAMPLE* |
| | |
| | ** IF THERE ARE QUESTIONS, IT IS RECOMMENDED TO CONTACT |
| | REVIEWER. |
| | |
| | 4) NOTE: PLEASE SEE NFPA-101 7.10.8.3.1, .2. ANY EXIT |
| | WHICH COULD BE MISTAKEN FOR AN EXIT IN AN EMERGENCY |
| | SHALL BE IDENTIFIED WITH SIGNS PER SECTIONS NOTED. |
| | PLEASE PLACE NOTES ON ELECTRICAL PLANS ALONG WITH LIFE |
| | SAFETY PLANS FOR WORDS OF NO EXIT IN MINIMUM SIZE |
| | REQUIREMENTS. |
| | |
| | 5) NOTE: PLEASE PROVIDE PHOTO-METRIC LEVELS FOR ALL |
| | DESIGNATED EGRESS PATHS UNDER NORMAL AND EMERGENCY |
| | CONDITIONS. PLEASE KEEP IN MIND THAT NO LIGHTING |
| | CONTROL OR DIMMING SYSTEM IS PERMITTED TO DIMINISH |
| | LIGHTING LEVELS BELOW THE MINIMUM. THIS SHALL BE SET |
| | AND SHALL NOT BE OVER RIDDEN. PLEASE SEE THAT ALL STAIR |
| | AREAS/STEPS SHALL CONTAIN THE MINIMUM OF 10FT CANDLES |
| | UNDER NORMAL AND IS PERMITTED TO GO DOWN TO 1FT CANDLE |
| | UNDER AN EMERGENCY. |
| | PLEASE SEE 7.8.1.3, 7.9.1.2, .2.2. PLEASE ALSO SEE |
| | 7.8.1.2.2 FOR ANY REQUIRED EGRESS LIGHTING ON OCCUPANCY |
| | CONTROLS WHICH SHALL FAIL SAFE *ON*. |
| | |
| | 6) NOTE: THE RISER, LOAD CALCULATIONS AND PANEL |
| | SCHEDULES SUBMITTED ALL NEED TO BE COMPLETE WITH THE |
| | FOLLOWING INFORMATION FOR REVIEW. |
| | FOR EXAMPLE: |
| | |
| | A) PLEASE SEE RISER ON SHEET E-7.0 WHICH CLEARLY |
| | INDICATES PANEL *HVPP* FEEDING 150KVA TRANSFORMER WITH |
| | A 250AMP BREAKER. HOWEVER PANEL SCHEDULE FOR THIS SAME |
| | *HVPP* DOES NOT LIST ANY SUCH BREAKER OR FEED TO THE |
| | TRANSFORMER.??? |
| | |
| | B) PLEASE PROVIDE INFORMATION FOR WHERE *LVMDP* IS |
| | BEING FED FROM. |
| | |
| | C) PLEASE SEE *HVPP* WHICH DOES NOT INCLUDE ANY OF THE |
| | LOADS FOR THE LVMDP SUCH AS LIGHTING. |
| | |
| | D) THERE IS NO INFORMATION ON WHERE PANELS *H1 OR H2* |
| | ARE BEING FED FROM. ARE THESE FROM OTHER SERVICES? ARE |
| | THESE FROM MULTIPLE TENANT METERS? |
| | ARE MAINS GROUPED? LABELED? BONDED SERVICES? ETC |
| | |
| | E) RISER INDICATES #3 AWG AS THE SIZE OF THE NEW |
| | FEEDERS TO THE NEW PANEL *C* YET *LVMDP* INDICATES |
| | *3/0*AWG. THIS IS SUBSTANTIALLY DIFFERENT. |
| | PLEASE COORDINATE. |
| | |
| | F) RISER INDICATES THAT PANEL K IS BEING FED FROM THE |
| | TRANSFORMER AND PANEL H1. HOWEVER PANEL H1 STATES A |
| | FEED TO PANEL *P* NOT TO PANEL *K*. |
| | |
| | G) PANEL *P* IS SHOWN WITH FEED-THRU LUGS ON SCHEDULE |
| | HOWEVER THIS PANEL IS NOT SHOWN ON RISER FEEDING THRU |
| | TO ANY OTHER PANEL. IS THIS THE CASE? |
| | |
| | H) TRACK LIGHTING LOADS ARE NOT SHOWN PER 220.43B |
| | |
| | I) SHOW WINDOW LOADS NOT SHOWN PER 220.43A |
| | |
| | J) SHOW LOCATIONS OF ALL TRANSFORMERS ON |
| | PLANS.450.13,450.21,240.21, 310.16 ETC TO BE REVIEWED |
| | ALONG WITH 110.26, 450.9. |
| | RISER INDICATES THE 150KVA TRANSFORMER WHICH FEEDS FROM |
| | HVPP TO LVMDP, YET THE PLANS DOES NOT INDICATE THIS |
| | TRANSFORMER ANYWHERE NEAR THE PROXIMITY OF EITHER OF |
| | THESE. SEE 240.21 FOR TAPPED CONDUCTORS. |
| | |
| | K) PLEASE PROVIDE ALL CONDUCTORS ON THE SECONDARY SIDE |
| | OF THE TRANSFORMERS. SEE 240.21,310.16,240.4. |
| | |
| | *** PLEASE COORDINATE ALL OF THE ELECTRICAL SYSTEMS AND |
| | SUBMIT A COMPLETE RISER WITH LOAD CALCULATIONS AND |
| | SIZES FOR ALL SYSTEMS. |
| | SEVERAL EXAMPLES ARE GIVEN ABOVE TO SOME OF THE ITEMS |
| | WHICH ARE NOT COORDINATED OR PROVIDED. THERE ARE MANY |
| | ITEMS WHICH CAN NOT BE REVIEWED FOR MINIMUM CODE |
| | COMPLIANCE AT THIS TIME. THESE ARE SOME EXAMPLES ONLY |
| | AND ARE IN NO WAY ALL. |
| | |
| | PLEASE SEE 220, 230.70, 230.71,230.72, 230.2E,310.16, |
| | 240.21 ETC. THERE ARE TOO MANY SECTIONS TO NOTE. |
| | FBC 106.1.1,106.1.2,106.3.5.1.2 FOR CLARITY, |
| | COORDINATION OF RECORD PLANS. |
| | |
| | 7) NOTE: PLEASE SEE 13-415.AB.1.1,.1.2 AND .1.3 FOR |
| | LIGHTING CONTROLS. PLEASE SEE SECTION 13-415.AB.1.3 |
| | SPECIFICALLY FOR CONTROLS. |
| | ALSO SEE ITEMS LIKE THE FAN LIGHTS WHICH ARE SHOWN ON |
| | FAN CONTROLS. |
| | OTHER FIXTURES SUCH AS FIXTURES F AND OTHER LOCATIONS |
| | WHICH INDICATE OVER RIDES AS STANDARD SINGLE POLE |
| | SWITCH PER SYMBOL LEGEND WHICH IS NOT PERMITTED. |
| | |
| | 8) NOTE: PLEASE SEE 13-415.AB.1.4 FOR EXTERIOR LIGHTING |
| | CONTROLS. |
| | |
| | |
| | 9) NOTE: PLEASE SEE 210.8B2 FOR WET BAR AND KITCHEN |
| | AREA GFI PROTECTION REQUIRED. |
| | |
| | 10) NOTE: PLEASE SEE NOTES ON E-4.0 WHICH INDICATE CODE |
| | SECTIONS FROM PREVIOUS FLORIDA BUILDING CODE. SUCH AS |
| | SECTIONS NOTED: 13-415.1.ABC.3. |
| | |
| | 11) NOTE: PLEASE SHOW ALL DEVICES FOR FIRE ALARM HORNS, |
| | STROBES, ETC MEETING ADA PER FBC CHAPTER 11. EVEN AS |
| | THE FA SYSTEM/SCOPE IS UNDER SEPARATE PERMIT, PER FS |
| | 633 MINIMUM DESIGN FOR FIRE AND LIFE SAFETY SHALL BE ON |
| | BASE PLANS. PLEASE SEE FBC 11-4.28.1,.2 AND .3. |
| | |
| | AS NOTED ABOVE, THERE ARE SEVERAL ITEMS IN NEED OF |
| | COORDINATION AND INFORMATION TO BE SUBMITTED FOR |
| | REVIEW. THERE MAY BE NEW COMMENTS ON THE NEXT REVIEW. |
| | |
| | ** PER BUILDING OFFICIAL PLANS ARE NO LONGER RELEASED. |
| | ALL SHEETS TO BE REVISED OR CHANGED OUT IN THIS OFFICE. |
| | |
| | |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | |