| Plan Review Notes For Permit 09080074 |
| Permit Number |
09080074 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-08-05 10:33:23 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING | | | CODE | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | | | | 1. PROVIDE A REASONABLE VALUE FOR THIS JOB. | | | | | | 2. SCOPE NOT CLEAR. PROVIDE A FLOOR PLAN SHOWING | | | LOCATION OF PROPOSED WORK. SHOW ALL WINDOW LOCATIONS, | | | WINDOW SIZES, DOOR LOCATIONS, DOOR SIZES. IS THE DOOR | | | AT A REQUIRED ACCESSIBLE ENTRANCE/EXIT? | | | | | | 3. PROVIDE BUILDING HEIGHT FBC1609. | | | | | | 4. DOOR CONFIGURATION IS NOT CLEAR. BASED ON THE | | | DRAWING, IT APPEARS THAT ONE LEAF IS 5', THE SECOND IS | | | 33". IS THAT CORRECT? | | | | | | 5. INDICATE OPTIONS PROPOSED ON THE PRODUCT APPROVAL. | | | DESIGN PRESSURE REQUIRED IS NOT CLEAR AT THIS TIME, | | | FBC1609. | | | | | | 6. PROVIDE A STRUCTURAL DETAIL FOR THE ALTERED OPENING, | | | FBC1609. | | | | | | | | | | | | |
|