| 2009-08-05 09:47:14 | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009 |
| | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND |
| | FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | ALL COMMENTS RELATE TO SHEET, UNLESS OTHERWISE NOTED. |
| | ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS |
| | OTHERWISE NOTED. |
| | |
| | 1} THE RISER DIAGRAM SUBMITTED IS NOT CLEAR ENOUGH TO |
| | REVIEW. TWO ARE SUBMITTED ON OPPOSITE SIDES AND THE |
| | SAME PLAN, WHICH IS TO BE USED. |
| | |
| | 2} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, |
| | METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT |
| | COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED. |
| | |
| | 3} INDICATE IF THE ELECTRICAL SERVICE SHOWN ON THE PLAN |
| | IS NEW OR EXISTING. IF NEW PROVIDE AN AIC RATING, AND |
| | LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, METER |
| | ENCLOSURE, DISCONNECTS AND PANELS, SO THAT COMPLIANCE |
| | WITH ARTICLES 225 AND 230 CAN BE REVIEWED. PROVIDE A |
| | RISER DIAGRAM WITH CONDUCTOR AND CONDUIT SIZE AND |
| | TYPE. |
| | |
| | 4} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.2 |
| | RESIDENTIAL FLORIDA BUILDING CODE. |
| | |
| | 5} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN. |
| | ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER |
| | 440.14, RECEPTACLE PER 210.63, LIGHT PER 210.70(A) (3) |
| | IF APPLICABLE. |
| | |
| | 6} PLEASE INCLUDE THE ADDRESS OF THE PROJECT ON THE |
| | PLANS FOR RECORD RETENTION.106.1.3.FBC AS AMENDED. |
| | |
| | 7} 106.1 SUBMITTAL DOCUMENTS. CONSTRUCTION DOCUMENTS, |
| | SPECIAL INSPECTION AND STRUCTURAL OBSERVATION PROGRAMS, |
| | AND OTHER DATA SHALL BE SUBMITTED IN TWO OR MORE SETS |
| | WITH EACH APPLICATION FOR A PERMIT. |
| | |
| | 8} LABEL ALL ROOMS FOR CLARITY, RECORD RETENTION AND SO |
| | OUTLET REQUIREMENTS OF 210.52 CAN BE REVIEWED. |
| | |
| | 9} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN |
| | THE FIELD WHEN WORKING FROM THIS DOCUMENT THE PLANS |
| | MUST BE DRAWN IN INK OR ON A CAD MACHINE TO PREVENT |
| | THEM FROM BEING ALTERED. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW. |