Plan Review Notes For Permit 09070792
Permit Number 09070792
Review Stop B
Sequence Number 1
Notes
Date Text
2009-08-05 09:53:55RE-ROOF BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- NOA 04-0723.01 SUBMITTED EXPIRED ON 04/16/09. NEED
 TO PROVIDE CURRENT NOA.
  
 2- CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO
 BE INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. 1609 FBC 2007.
  
 3- CLEARLY IDENTIFY WHICH FASTENING OPTION IS GOING TO
 BE USED.
  
 4- PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7.
 NOTE: IF SELECTED ASSEMBLY IS LIMITED BY GENERAL
 LIMITATION #9, THEN IT MAY NOT BE USED IN THIS PROJECT.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712