| Plan Review Notes For Permit 09070791 |
| Permit Number |
09070791 |
|
| Review Stop |
ENG |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-08-18 14:00:12 | DETAIL DRAWING SHOWS ENOUGH INFORMATION TO FAIL THE | | | PERMIT. THE ALLEY RIGHT-OF-WAY (ROW) IS 14', THE EDGE | | | OF THE ROW IS NOT THE FENCE LINE WHERE THEY ARE SHOWING | | | INSTALLING THE PAD, CABINET, UNDERGROUND CONDUITS. ALL | | | APPEAR TO BE LOCATED ON TWO SEPARATE PRIVATE PROPERTIES | | | WITHOUT EASEMENTS (440 & 442 -27TH STREET). | | | SUPPLY EASEMENTS ON DRAWINGS OR SHOW ALL MATERIALS IN | | | THE DEDICATED 14' ALLEY ROW. | | | DO NOT RESUBMIT SHOWING THE CABINETOR PAD IN THE | | | DEDICATED ALLEY ROW, IT IS TOO WIDE AND WILL BE AN | | | IMPEDIMETE TO TRAFFIC. | | | | | | SHOWING THE EDGE OF PAVEMENT (FOR THE ALLEY) DOES NOT | | | DESIGNATE IT TO BE 1' FROM THE ROW. | | | | | | FORWARDING PERMIT APPLICATION TO BUILDING CABINET MAY | | | NEED TO HAVE WIND LOADS SUPPLIED. |
|