| Plan Review Notes For Permit 09070777 |
| Permit Number |
09070777 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-08-05 19:40:33 | PASSED WITH THE FOLLOWING CONDITIONS: | | | | | | 1. PROVIDE PRODUCT APPROVALS FOR BUILDING PLAN REVIEW | | | PER FAC-RULE 9B-72. PAGE M-2 SHOWS TWO NEW WALL | | | LOUVERS. | | | | | | 2. PROVIDE TEST AND BALANCE REPORT AT TIME OF FINAL | | | INSPECTION TO VERIFY VENTILATION AIRFLOW RATES IN | | | ACCORDANCE WITH ASHRAE 62.1-2004 SECTION 7.2.2. | | | | | | 3. HP-1 REQUIRES A DUCT MOUNTED SMOKE DETECTOR | | | INSTALLED AND CONNECTED TO BUILDING FIRE ALARM SYSTEM | | | IN ACCORDANCE WITH FBC-M 606.2.1 AND 606.4. | | | | | | 4. ENERGY CALCULATIONS NOT REVIEWED AS PART OF THIS | | | PERMIT FOR COMPLIANCE WITH THE MECHANICAL PROVIDIONS OF | | | THE FLORIDA ENERGY CODE. COOLING LOAD CALCULATIONS HAVE | | | BEEN DETATCHED FROM ENERGY CALCULATIONS AND RETAINED AS | | | PART OF THIS PERMIT RECORD DUE TO INCREASED COOLING | | | LOADS ASSOCIATED WITH ADDED OUTSIDE AIR. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|