| 2010-02-25 17:00:34 | ** DENIED ** |
| | |
| | |
| | 1) NOTE: THERE ARE THREE NEW BOOKS SUBMITTED WITH TWO |
| | SETS OF FLA COM CALCULATIONS IN EACH OF THE NEW BLUE |
| | BINDER BOOKS. |
| | ONE SET FOR METHOD A FOR WHOLE BUILDING COMPLIANCE AND |
| | ONE SET OF METHOD B FOR RENOVATIONS/PRESCRIPTIVE |
| | REQUIREMENTS. |
| | PLEASE SEE PAGE TWO OF THE FLA COM CALCULATIONS. THIS |
| | REQUIRES THE INPUT DATA REPORT TO BE SUBMITTED WITH |
| | EACH OF THE FLA COM SUMMARY SHEETS COMPLIANCE REPORTS. |
| | NO INPUT DATA REPORT SHEETS WERE SUBMITTED. THIS OFFICE |
| | CAN NOT CONFIRM OR REVIEW FOR MINIMUM CODE COMPLIANCE. |
| | |
| | **METHOD B PRESCRIPTIVE FOR NEW BEING CHANGED OUT OR |
| | INSTALLED MUST BE USED INSIDE THE EXISTING STORE AREAS. |
| | 13-400.B.0.4. |
| | PLEASE SEE 13-415.AB.5, 13-415.AB.5.1, 13-415.B.1 AND |
| | APPENDIX B 4.1.1 FOR INTERIOR. |
| | PLEASE SEE 13-415.AB.2.2 FOR EXTERIOR. |
| | |
| | **THE SUBMITTED METHOD *A* MAY BE USED FOR NEW |
| | CONSTRUCTION OF WHOLE BUILDINGS, NEW ADDITIONS/AIR |
| | CONDITIONED PORTIONS OF EXISTING BUILDINGS. |
| | IN EITHER CASE WHEN USING METHOD *A* ALL PORTIONS AND |
| | COMPONENTS OF THAT NEW AREA ARE REQUIRED TO BE ENTERED |
| | INTO THE IDR FOR COMPLIANCE. |
| | |
| | ** I NOTICED IN ONE OF THE SUMMARY REPORTS THE USE OF * |
| | LIGHTING DESIGNATED AS REQUIRED BY HEALTH OR LIFE |
| | SAFETY STATUTE, ORDINANCE OR OTHER REGULATION. |
| | THIS MAY NOT BE USED AS THERE ARE NO SUCH ADOPTED |
| | ALLOWANCES FOR THE STORE LOCATION KNOWN TO THIS OFFICE. |
| | |
| | |
| | 2) NOTE: SIDE NOTE, THIRD COPY IS A PHOTO-COPY OF |
| | SIGNED AND SEALED COMPLIANCE REPORTS FOR METHOD *A*. |
| | ONLY TWO COMPLETE SETS ARE NEEDED HOWEVER IF A THIRD |
| | COPY IS NEEDED FOR YOUR RECORDS OR STAMPING THEN THE |
| | SETS MUST BE ORIGINAL. |
| | |
| | 3) NOTE: NO LICENSED CONTRACTOR HAS APPLIED FOR PERMIT |
| | AS OF YET. REVIEW TO REMAIN IN FAILED STATUS UNTIL |
| | COMMENTS HAVE BEEN ADDRESSED AND LICENSED CONTRACTOR |
| | CAN BE VERIFIED. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |