| 2009-12-19 14:43:01 | REVIEW #: 2ND |
| | ACTION: DENIED |
| | |
| | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | PREVIOUS REVIEW COMMENTS FOR CONTINUITY: |
| | |
| | 1. OK |
| | |
| | 2. OK |
| | |
| | 3. **NOT ADDRESSED** NOTE 15.710 ON PG M2 CALLS FOR FAN |
| | TO RUN CONTINUOUSLY DURING OPERATION, BUT THERE IS NO |
| | INDICATION ON PLANS AS TO HOW THIS WILL BE |
| | ACCOMPLISHED. ALSO, NOTE H ON PAGE M4 EF SCHEDULE CALLS |
| | FOR INTERLOCK WITH MUA FANS. THIS IS A DIFFERENT |
| | REQUIREMENT FROM THE INTERLOCK WITH COOKING APPLIANCES |
| | AS REQUIRED PER FNC-M 507.2.1.1. KITHCEN HOOD EXHAUST |
| | SYSTEM IS NO LONGER PART OF THIS REVIEW. PROVIDE |
| | SEPARATE PLANS AND PERMIT APPLICATIONS FOR COMMERCIAL |
| | KITCHEN HOOD EXHAUST SYSTEMS AND HOOD SUPPRESSION |
| | SYSTEMS. |
| | |
| | 4. **NOT ADDRESSED** THE CUT SHEETS PROVIDED DO NOT |
| | CONTAIN ANY INFORMATION FROM THE APPLIANCE |
| | MANUFACTURERS REGARDING THE WIND RESISTANCE |
| | CAPABILITIES OF THE APPLIANCES. PROVIDE MANUFACTURER'S |
| | DATA SHOWING ALL OUTDOOR APPLIANCES (RTU, EF, |
| | CONDESNER, ETC.) ARE DESIGNED FOR WIND RESISTANCE IN |
| | ACCORDANCE WITH FBC-M 301.12. |
| | |
| | 5. ENERGY CALCULATIONS: UPDATED FORM 400B-08 WAS |
| | PROVIDED, HOWEVER, THE CERTIFICATION PAGE IN THE CODE |
| | COMPLIANCE FORM IS A PHOTOCOPY. PROVIDE ORIGINAL SIGNED |
| | AND SEALED CODE COMPLIANCE FORMS IN ACCORDANCE WITH |
| | FBC-B 13-103.2. ALSO, ENERGY CALCULATIONS DO NOT |
| | INCLUDE THE NEW RTU 25. PLANS AND ENERGY CALCULATIONS |
| | SHALL MATCH IN ACCORDANCE WITH 13-103.2. |
| | |
| | 6. **NOT ADDRESSED** NO COOLING LOAD CALCULATIONS COULD |
| | BE FOUND IN THE SUBMITTED PACKAGE. COOLING LOAD |
| | CALCULATIONS SHALL BE APENDED TO THE ENERGY CODE |
| | COMPLIANCE FORM IN ACCORDANCE WITH FBC-B 13-407.AB.1. |
| | |
| | NOTE: SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE |
| | COMMERCIAL KITCHEN HOOD EXHAUSTSYSTEMS, HOOD |
| | SUPPRESSION SYSTEMS, AND REMOTE REFRIGERATION SYSTEMS. |
| | |