Plan Review Notes
Plan Review Notes For Permit 09070775
Permit Number 09070775
Review Stop G
Sequence Number 2
Notes
Date Text
2009-12-16 12:05:04DENIED
 REFERENCE: FBC-2007 FUEL GAS
  
 ****FROM PREVIOUS REVIEW:
  
 A. SHEETS M2 & M3.1 SHOW A GAS PIPING RISER DIAGRAM & A
 GAS EQUIPMENT DETAIL. ALL NATURAL OR LP GAS INFIRMATION
 SHALL BE SUBMITTED ON THE PLUMBING SHEETS AS IT IS IN
 THE SCOPE OF WORK OF THE PLUMBING CONTRACTOR. A
 SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED FOR THE GAS PERMIT:
  
 1. OK
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 ****RESPONSE NOTED, BUT THE PIPING MATERIAL WAS NOT
 FOUND IN THE SPECIFICATION BOOK. NO SECTION 15190 WAS
 INDICATED.
  
 3. OK
 4. OK
 5. OK
 6. OK
  
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. -- IF 2 PSI SUBMIT
 THE MANUF. SPECIFICATION SHEETS FOR THE REGULATORS.
 ****RESPONSE NOTED, BUT SINCE THIS IS A 2 PSI SYSTEM,
 THE REGULATORS SHALL BE INDICATED ON THE GAS ISOMETRIC
 RISER DIAGRAM. ALSO THE LOCATION FOR EACH MANUFACTURE &
 MODEL NUMBER SHALL BE INDICATED FOR EACH REGULATOR ON
 THE ISOMETRIC TO VERIFY COMPLIANCE OF USAGE AT EACH
 REGULATOR. THE MANUF SHEETS SHALL SHOW APPROVAL
 LISTING. THIS IS NOT SHOWN OR INDICATED ON THE
 REGULATOR SPEC SHEET. (P4, NOT M4 AS INDICATED IN THE
 RESPONSE).
  
 8. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2007 FUEL GAS CODE
 SECS. 502 THRU 505 & RESIDENTIAL CODE SECS. G2426 THRU
 G2429.
 ****RESPONSE NOTED, BUT 4-M3.1DOES NOT INDICATE THE
 INFORMATION REQUESTED IN COMMENT. PLEASE SHOW
 INFORMATION REQUESTED.
  
 9. OK
 10. N/A
 11. N/A
  
 12. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. -- UNION NOT INDICATED.
 ****RESPONSE NOTED, BUT UNION NOT SHOWN IN DETAIL
 3-MP1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved