Plan Review Notes
Plan Review Notes For Permit 09070775
Permit Number 09070775
Review Stop E
Sequence Number 2
Notes
Date Text
2009-12-16 15:29:07 
 ** DENIED **
  
 **** IMPORTANT**
 1) NOTE: AS NOTED PREVIOUSLY THE BREAKERS WHICH ARE IN
 THE ELECTRICAL SERVICE EQUIPMENT WHICH ARE NOT RATED
 FOR THE AVAILABLE FAULT CURRENT NEED TO BE CHANGED OUT.
 THIS IS A FIRE AND LIFE SAFETY HAZARD. THIS OFFICE HAS
 SEEN FAULTS ON ELECTRICAL SYSTEMS WHICH HAVE RESULTED
 IN FIRE, INJURY AND LOSS OF LIFE. THESE CAN BE CHANGED
 OUT UNDER A SEPARATE PERMIT BEFORE CONSTRUCTION BEGINS
 FOR THE REMAINDER OF THE PROJECT. PLEASE SUBMIT PERMIT
 APPLICATION AND SPECS/CUT SHEETS ON BREAKERS AND PERMIT
 WILL BE DONE ON A TURN AROUND BASIS. NOTICE HAS BEEN
 GIVEN IN PREVIOUS REVIEW AND NO PERMIT APPLICATION HAS
 BEEN MADE TO RESOLVE SAFETY CONCERNS. THE NEXT STEP
 WILL BE TO ISSUE CORRECTION NOTICE TO STORE LOCATION.
 PLEASE OBTAIN PERMIT AND CHANGE OUT BREAKERS AS SOON AS
 POSSIBLE. THE DISCONNECTION OF UTILITY SOURCE BASED ON
 LIFE SAFETY CONCERNS IS POSSIBLE IF THIS IS NOT DONE IN
 A TIMELY FASHION. PLEASE CALL TO GO OVER TO ALLEVIATE
 ANY POSSIBLE DELAYS. NEC 110.9
  
 2) NOTE: AS GONE OVER WITH THE STRUCTURAL ENGINEER,
 SHEET S6.3 CONTAINS THE OLD SEAL WITH THE WORDING
 *CERTIFICATE* INSTEAD OF THE NEW SEAL. A NEW SHEET IS
 TO BE REPLACED INTO SETS.
  
 3) NOTE: THE SUBMITTED ENERGY CALCULATIONS ARE NOT ALL
 ORIGINALS. IN FACT ONLY ONE SET SUBMITTED CONTAINS THE
 ORIGINAL SIGNATURE AND SEAL OF DESIGN PROFESSIONALS.
 THE OTHER TWO REQUIRED COPIES ARE ACTUALLY PHOTO-COPIES
 OF THE SIGNED AND SEALED ORIGINALS. THE CERTIFICATION
 SHEETS ARE ALL REQUIRED TO CONTAIN ORIGINAL SIGNATURE,
 DATE AND SEAL.
 FAC 61G15-23.002, FS471.025
  
 4) NOTE: THE SUBMITTED ENERGY PERFORMANCE CALCULATIONS
 CONTAIN A SIGNATURE FROM THE PERSON WHO PREPARED
 DOCUMENTS NOT AS ONE OF THE LICENSED DESIGN
 PROFESSIONALS LISTED ON PROJECT. THE ONLY PERSON
 PERMITTED TO PREPARE DOCUMENTS IS THAT LISTED AS THE
 LICENSED DESIGN PROFESSIONAL AS REQUIRED UNDER FBC
 13-103.1, FS 471.005. FS 481.221, FAC 61G15-23.002.
  
 5) NOTE: PREVIOUS REVIEW GAVE CODE SECTIONS FOR
 REQUIRED LIGHTING CONTROLS. RESPONSE STATES THE CODE IS
 MET HOWEVER BASED ON THE PLANS AND RESPONSE THERE IS
 STILL SOME ITEMS WHICH NEED TO BE ADDRESSED. FBC
 13-415.AB1.1 FIRST REQUIRES *ALL* LIGHTING IN BUILDING
 GREATER THAN 5K SQ FT TO BE AUTOMATICALLY CONTROLLED.
 THE CODE DOES GIVE DIFFERENT WAYS IN DOING THIS AND
 SOME EXCEPTIONS. HOWEVER THE INTENT OF THE ENERGY CODE
 IS TO SAVE ENERGY BY TURNING OFF ALL LIGHTING.
  
 SECTION 13-415.AB.1.2 REQUIRES EACH SPACE TO HAVE ITS
 OWN MANUAL CONTROL TO BE CAPABLE OF OVER RIDING ANY
 TIME OF DAY SCHEDULING SYSTEM OR IT MAY BE A SEPARATE
 CONTROL FOR SPACE SUCH AS TIMED OR OCCUPANCY SENSORS.
 IN EITHER CASE THIS DOES NOT MEAN INDIVIDUAL MANUAL
 CONTROL SUCH AS SINGLE POLE SWITCHES.
 SUCH LOCATIONS WOULD BE THE JANITOR CLOSET, MEAT
 COOLER, PRODUCE COOLER, MEAT PREP, UTILITY ROOM,
 PHOTO-LAB AREA, ROTISSERIE PREP, AND BAKER FREEZER.
 ** ALL SPACES.
  
 6) NOTE: PREVIOUS REVIEW REQUESTED TO INDICATE WHETHER
 OR NOT THE CONTINUOUS LOADS ARE ALREADY FIGURED AT
 125%. THE RESPONSE STATES SOME INFORMATION ABOUT THE
 AIR CURTAIN FOR THE DOORS. THIS WAS NOT PART OF THE
 ORIGINAL COMMENT.
 PLEASE SEE 215.3, 230.42 ETC FOR ALL CONTINUOUS LOADS
 WHICH ARE REQUIRED TO BE SHOWN AND FIGURED AT 125%.
  
 7) NOTE: COVER SHEET STATES A 2006 FLORIDA BUILDING
 CODE. THIS COULD BE REDLINED ON PLANS.
  
 8) NOTE: PLEASE SEE 13-415.AB.5, 13-415.AB.2.2 FOR
 EXTERIOR PERFORMANCE CALCULATIONS FOR PRESCRIPTIVE
 REQUIREMENTS. PLEASE EXPLAIN HOW THE INPUT DATA REPORT
 CAN BE BLANK FOR EXTERIOR LIGHTING WHEN THERE IS NEW
 LIGHTING BEING INSTALLED ON PLANS?
  
 ** COMMENTS: 1,2,3,4 AND 8 4 MUST BE ADDRESSED AT THIS
 TIME. COMMENTS #5 AND 6 CAN BE DONE AS A PROVISO WHICH
 WOULD ALLOW ISSUANCE OF PERMIT AND GIVE DESIGN TEAM
 TIME TO REVISE PLANS WITHIN A SPECIFIED TIME FRAME.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  