2009-12-28 13:27:39BUILDING PLAN REVIEW
 PERMIT: 09070775
 ADD: 4295 45TH ST
 CONT: TO BE DETERMINED
 TEL: (561)856-6655 NEYITA LEIVA
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 DEC. 28/ 2009
 2ND REVIEW
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) SUBMITTED ENERGY CALCS FORM 400B-2008. THIS FORM
 PLEASE SEE BOTH THE ELECTRICAL AND MECHANICAL COMMENTS
 ON THE REQUIRED SIGNATURE AND SEAL REQUIREMENTS.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 FL ADMIN CODE 61G16.003 ARCHITECTS
  
 3-4) COMPLIED.
  
 5) PROVISO: ADDITION IS LOCATED WITHIN A FLOODZONE A8
 AT WITH A REQUIRED ELEVATION OF 15.5 FT NGVD, FBC
 BUILDING 3110.1.2 / CITY OF WPB CODE OF ORDINANCES
 SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED.
  
 6) PLEASE NOTE THAT PRODUCT APPROVALS WILL NOT BE
 REQUIRED AT TIME OF PERMITTING BUT WILL BE REQUIRED FOR
 FULL REVIEW.
  
 BUILDING PROVISO:FL BLD CODE 1609.6.2.2 COMPONENTS &
 CLADDING, PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT
 INSPECTOR OF PRODUCT TESTING REPORTS, MISSING REPORTS
 ARE AS FOLLOWS:
 A) EXTERIOR GLAZED WINDOWS
 B) MULLION
 C) EXTERIOR GLAZED DOORS, AUTOMATIC SLIDDING GLASS
 DOORS W/ TRANSOM
 D) OVERHEAD DOORS
 E) WALL LOUVERS
 F) EFIS SYSTEMS
 G) ROOFING ASSEMBLIES INCLUDING ROOF INSULATION
 H) PERMANUFACTURED A/C STANDS
  
 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 7) PARTIAL APPROVAL, ENGINEERING CALCULATIONS WERE
 SUBMITTED FOR THE ATTACHMENT OF THE CURB TO ROOF
 FRAMING MEMBERS WIWTH A CLIP SYSTEM, PRODUCED BY ICR
 ENGINEERING, INC. THE CALCULATIONS ARE NOT SIGNED NOR
 SEALED NOR DO THEY PROVIDE A SIGNED AND SEALED COVER
 SHEET.
  
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
  
 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR INDEX
 SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED AND
 THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE
 PRODUCTION & PREPARATION OF EACH SECTION OF THE
 ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION
 ON THE COVER SHEET OR INDEX.
  
 A3.3 PLEASE NOTE THAT ROOF TOP MECHANICAL EQUIPMENT
 MUST MEET THE WIND REQUIREMENTS IN CHAPTER 16 OF FBC.
 301.13 FBC MECHANICAL. WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST WIND
 PRESSURES ON THE EQUIPMENT AND THE SUPPORTS AS
 DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, BUILDING. NOTE THE STRUCTURAL SHEETS INDICATE THE
 CURB ATTACHMENTS TO THE ROOF DECK BUT NOT THE UNIT TO
 THE ROOF CURB.
  
 2ND REQUEST, FOR ALL ROOFTOP EQUIPMENT PLEASE PROVIDE
 EITHER BY TESTING, CALCULATIONS OR RATIONAL ANYLSIS THE
 EXTERIOR ELEMENTS (CABINETS)OF THE ROOF TOP EQUIPMENT
 ARE DESIGNED TO WITHSTAND THE WIND REQUIREMENTS OF
 CHAPTER 16 OF THE FLORIDA BUILDING CODE BUILDING AS
 REQUIRED BY SECTION 301.13 FBC MECHANICAL CODE.
  
 8) COMPLIED.
  
 9) 2ND REQUESST, PLANS INDICATE THE USE OF WALK IN
 COOLERS ( AGA1) PLEASE PROVIDE DOCUMENTATION THAT THE
 THERMA- STRUCTURE COOLERS COMPLIES WITH SECTION
 2603.4.1.2 (1-4). SUBMITTALS FOR FREZZER CASES WERE
 FOUND BUT NOT FOR THE WALK IN COOLERS.2603.4.1.2 COOLER
 AND FREEZER WALLS. FOAM PLASTIC INSTALLED IN A MAXIMUM
 THICKNESS OF 10 INCHES (254 MM) IN COOLER AND FREEZER
 WALLS SHALL:
  
 1. HAVE A FLAME SPREAD INDEX OF 25 OR LESS AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450, WHERE
 TESTED IN A MINIMUM 4 INCH (102 MM) THICKNESS.
  
 2. HAVE FLASH IGNITION AND SELF-IGNITION TEMPERATURES
 OF NOT LESS THAN 600??F AND 800??F (316??C AND 427??C),
 RESPECTIVELY.
  
 3. HAVE A COVERING OF NOT LESS THAN 0.032-INCH (0.8 MM)
 ALUMINUM OR CORROSION-RESISTANT STEEL HAVING A BASE
 METAL THICKNESS NOT LESS THAN 0.0160 INCH (0.4 MM) AT
 ANY POINT.
  
 4. BE PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM. WHERE
 THE COOLER OR FREEZER IS WITHIN A BUILDING, BOTH THE
 COOLER OR FREEZER AND THAT PART OF THE BUILDING IN
 WHICH IT IS LOCATED SHALL BE SPRINKLERED.
  
  
 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 11) NEW COMMENT SHEET S6.3 PLEASE SEE FBC* 106.1 THE
 NEW TYPE OF ENGINEER'S SEAL IS REQUIRED FOR ALL PLANS
 SEALED AFTER 12/31/05. ENGINEER'S SEALS INCLUDING THE
 WORD "CERTIFICATE" ARE NO LONGER VALID. ON 2/5/04 THE
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS AMENDED THE
 'SEALS' RULE AND REQUIRED THAT ALL MEMBERS OBTAIN SEALS
 WITH THE WORD "LICENSE" INSTEAD OF "CERTIFICATE". THE
 EXTENDED GRACE PERIOD FOR COMPLIANCE ENDED ON 12/31/05.
 (REF: 471.025 F.S. AND RULE 61G15-23.001 F.A.C.)
  
 RULE 61G15-23.001(1) F.A.C. THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS HAS CLEANED UP THE APPEARANCE
 OF THE SEAL BY ELIMINATING OBSOLETE CONTENT AND
 CHANGING THE WORD "CERTIFICATE" TO "LICENSE". A GRACE
 PERIOD RAN THROUGH DEC. 31,2005.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved