| 2009-12-28 13:27:39 | BUILDING PLAN REVIEW |
| | PERMIT: 09070775 |
| | ADD: 4295 45TH ST |
| | CONT: TO BE DETERMINED |
| | TEL: (561)856-6655 NEYITA LEIVA |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | DEC. 28/ 2009 |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. |
| | |
| | 2) SUBMITTED ENERGY CALCS FORM 400B-2008. THIS FORM |
| | PLEASE SEE BOTH THE ELECTRICAL AND MECHANICAL COMMENTS |
| | ON THE REQUIRED SIGNATURE AND SEAL REQUIREMENTS. |
| | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| | PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| | PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE |
| | DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. |
| | FL ADMIN CODE 61G15-23.002 ENGINEERS |
| | FL ADMIN CODE 61G16.003 ARCHITECTS |
| | |
| | 3-4) COMPLIED. |
| | |
| | 5) PROVISO: ADDITION IS LOCATED WITHIN A FLOODZONE A8 |
| | AT WITH A REQUIRED ELEVATION OF 15.5 FT NGVD, FBC |
| | BUILDING 3110.1.2 / CITY OF WPB CODE OF ORDINANCES |
| | SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD |
| | ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. |
| | |
| | 6) PLEASE NOTE THAT PRODUCT APPROVALS WILL NOT BE |
| | REQUIRED AT TIME OF PERMITTING BUT WILL BE REQUIRED FOR |
| | FULL REVIEW. |
| | |
| | BUILDING PROVISO:FL BLD CODE 1609.6.2.2 COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT |
| | INSPECTOR OF PRODUCT TESTING REPORTS, MISSING REPORTS |
| | ARE AS FOLLOWS: |
| | A) EXTERIOR GLAZED WINDOWS |
| | B) MULLION |
| | C) EXTERIOR GLAZED DOORS, AUTOMATIC SLIDDING GLASS |
| | DOORS W/ TRANSOM |
| | D) OVERHEAD DOORS |
| | E) WALL LOUVERS |
| | F) EFIS SYSTEMS |
| | G) ROOFING ASSEMBLIES INCLUDING ROOF INSULATION |
| | H) PERMANUFACTURED A/C STANDS |
| | |
| | 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| | REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITTING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 7) PARTIAL APPROVAL, ENGINEERING CALCULATIONS WERE |
| | SUBMITTED FOR THE ATTACHMENT OF THE CURB TO ROOF |
| | FRAMING MEMBERS WIWTH A CLIP SYSTEM, PRODUCED BY ICR |
| | ENGINEERING, INC. THE CALCULATIONS ARE NOT SIGNED NOR |
| | SEALED NOR DO THEY PROVIDE A SIGNED AND SEALED COVER |
| | SHEET. |
| | |
| | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS |
| | PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR |
| | PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE |
| | DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. |
| | FL ADMIN CODE 61G15-23.002 ENGINEERS |
| | |
| | 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR INDEX |
| | SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED AND |
| | THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE |
| | PRODUCTION & PREPARATION OF EACH SECTION OF THE |
| | ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION |
| | ON THE COVER SHEET OR INDEX. |
| | |
| | A3.3 PLEASE NOTE THAT ROOF TOP MECHANICAL EQUIPMENT |
| | MUST MEET THE WIND REQUIREMENTS IN CHAPTER 16 OF FBC. |
| | 301.13 FBC MECHANICAL. WIND RESISTANCE. MECHANICAL |
| | EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO |
| | WIND SHALL BE DESIGNED AND INSTALLED TO RESIST WIND |
| | PRESSURES ON THE EQUIPMENT AND THE SUPPORTS AS |
| | DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING |
| | CODE, BUILDING. NOTE THE STRUCTURAL SHEETS INDICATE THE |
| | CURB ATTACHMENTS TO THE ROOF DECK BUT NOT THE UNIT TO |
| | THE ROOF CURB. |
| | |
| | 2ND REQUEST, FOR ALL ROOFTOP EQUIPMENT PLEASE PROVIDE |
| | EITHER BY TESTING, CALCULATIONS OR RATIONAL ANYLSIS THE |
| | EXTERIOR ELEMENTS (CABINETS)OF THE ROOF TOP EQUIPMENT |
| | ARE DESIGNED TO WITHSTAND THE WIND REQUIREMENTS OF |
| | CHAPTER 16 OF THE FLORIDA BUILDING CODE BUILDING AS |
| | REQUIRED BY SECTION 301.13 FBC MECHANICAL CODE. |
| | |
| | 8) COMPLIED. |
| | |
| | 9) 2ND REQUESST, PLANS INDICATE THE USE OF WALK IN |
| | COOLERS ( AGA1) PLEASE PROVIDE DOCUMENTATION THAT THE |
| | THERMA- STRUCTURE COOLERS COMPLIES WITH SECTION |
| | 2603.4.1.2 (1-4). SUBMITTALS FOR FREZZER CASES WERE |
| | FOUND BUT NOT FOR THE WALK IN COOLERS.2603.4.1.2 COOLER |
| | AND FREEZER WALLS. FOAM PLASTIC INSTALLED IN A MAXIMUM |
| | THICKNESS OF 10 INCHES (254 MM) IN COOLER AND FREEZER |
| | WALLS SHALL: |
| | |
| | 1. HAVE A FLAME SPREAD INDEX OF 25 OR LESS AND A |
| | SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450, WHERE |
| | TESTED IN A MINIMUM 4 INCH (102 MM) THICKNESS. |
| | |
| | 2. HAVE FLASH IGNITION AND SELF-IGNITION TEMPERATURES |
| | OF NOT LESS THAN 600??F AND 800??F (316??C AND 427??C), |
| | RESPECTIVELY. |
| | |
| | 3. HAVE A COVERING OF NOT LESS THAN 0.032-INCH (0.8 MM) |
| | ALUMINUM OR CORROSION-RESISTANT STEEL HAVING A BASE |
| | METAL THICKNESS NOT LESS THAN 0.0160 INCH (0.4 MM) AT |
| | ANY POINT. |
| | |
| | 4. BE PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM. WHERE |
| | THE COOLER OR FREEZER IS WITHIN A BUILDING, BOTH THE |
| | COOLER OR FREEZER AND THAT PART OF THE BUILDING IN |
| | WHICH IT IS LOCATED SHALL BE SPRINKLERED. |
| | |
| | |
| | 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 11) NEW COMMENT SHEET S6.3 PLEASE SEE FBC* 106.1 THE |
| | NEW TYPE OF ENGINEER'S SEAL IS REQUIRED FOR ALL PLANS |
| | SEALED AFTER 12/31/05. ENGINEER'S SEALS INCLUDING THE |
| | WORD "CERTIFICATE" ARE NO LONGER VALID. ON 2/5/04 THE |
| | FLORIDA BOARD OF PROFESSIONAL ENGINEERS AMENDED THE |
| | 'SEALS' RULE AND REQUIRED THAT ALL MEMBERS OBTAIN SEALS |
| | WITH THE WORD "LICENSE" INSTEAD OF "CERTIFICATE". THE |
| | EXTENDED GRACE PERIOD FOR COMPLIANCE ENDED ON 12/31/05. |
| | (REF: 471.025 F.S. AND RULE 61G15-23.001 F.A.C.) |
| | |
| | RULE 61G15-23.001(1) F.A.C. THE FLORIDA BOARD OF |
| | PROFESSIONAL ENGINEERS HAS CLEANED UP THE APPEARANCE |
| | OF THE SEAL BY ELIMINATING OBSOLETE CONTENT AND |
| | CHANGING THE WORD "CERTIFICATE" TO "LICENSE". A GRACE |
| | PERIOD RAN THROUGH DEC. 31,2005. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | SURVEY: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |