Text |
| 2009-08-13 10:54:07 | DENIED |
| | REFERENCE: |
| | FBC-2007 PLUMBING |
| | FBC-2007 CHAPTER 1 |
| | |
| | 1. INFORMATIONAL: SEPARATE PERMITS ARE REQUIRED FOR THE |
| | TEMP. TOILET ROOM TRAILER & THE GREASE INTERCEPTORS. |
| | SECTION 105.1. |
| | |
| | 2. SHTS SP2.1, P1 & P3.1 DETAIL #2 A 2-WAY CLEANOUT IS |
| | REQUIRED ON THE INLET PIPING TO THE GREASE |
| | INTERCEPTORS. (UTILITY STANDARD) |
| | |
| | 3. SHTS SP2 COMPACTOR PAN PLAN INDICATES A DRAIN & |
| | SP2.1 DETAILS 2 & 3. PLEASE INDICATE IF THE COMPACTOR |
| | WILL BE COVERED AS TO NOT ALLOW STORM WATER TO ENTER |
| | THE DRAIN. THE DRAIN SHALL CONNECT TO THE GREASE |
| | INTERCEPTOR. IF THE STORM WATER WILL DRAIN AT THE |
| | COMPACTOR DRAIN, THEN THE DRAIN WILL HAVE TO BE |
| | DELETED. PLEASE CLARIFY. SECTION 106.1.2 (MORE INFO |
| | REQD). |
| | |
| | 4. SHT P2.1 DETAIL #1. SUBMIT CALCULATIONS FOR THE |
| | STORM DRAINAGE. SHOW THE SQUARE FOOT AREA OF THE ROOF |
| | PLUS 1/2 AREA OF ALL VERTICAL WALLS INCLUDING PARAPETS |
| | ADDED TO THE SQUARE FOOTAGE OF THE ROOF & TOTAL SQUARE |
| | FOOTAGE BEING DRAINED BY THE ROOF TABLE. TABLE 1106.3 & |
| | SECTIONS 1106.3 & 1106.4. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |