Plan Review Notes
Plan Review Notes For Permit 09070775
Permit Number 09070775
Review Stop P
Sequence Number 1
Notes
Date Text
2009-08-13 10:54:07DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 1
  
 1. INFORMATIONAL: SEPARATE PERMITS ARE REQUIRED FOR THE
 TEMP. TOILET ROOM TRAILER & THE GREASE INTERCEPTORS.
 SECTION 105.1.
  
 2. SHTS SP2.1, P1 & P3.1 DETAIL #2 A 2-WAY CLEANOUT IS
 REQUIRED ON THE INLET PIPING TO THE GREASE
 INTERCEPTORS. (UTILITY STANDARD)
  
 3. SHTS SP2 COMPACTOR PAN PLAN INDICATES A DRAIN &
 SP2.1 DETAILS 2 & 3. PLEASE INDICATE IF THE COMPACTOR
 WILL BE COVERED AS TO NOT ALLOW STORM WATER TO ENTER
 THE DRAIN. THE DRAIN SHALL CONNECT TO THE GREASE
 INTERCEPTOR. IF THE STORM WATER WILL DRAIN AT THE
 COMPACTOR DRAIN, THEN THE DRAIN WILL HAVE TO BE
 DELETED. PLEASE CLARIFY. SECTION 106.1.2 (MORE INFO
 REQD).
  
 4. SHT P2.1 DETAIL #1. SUBMIT CALCULATIONS FOR THE
 STORM DRAINAGE. SHOW THE SQUARE FOOT AREA OF THE ROOF
 PLUS 1/2 AREA OF ALL VERTICAL WALLS INCLUDING PARAPETS
 ADDED TO THE SQUARE FOOTAGE OF THE ROOF & TOTAL SQUARE
 FOOTAGE BEING DRAINED BY THE ROOF TABLE. TABLE 1106.3 &
 SECTIONS 1106.3 & 1106.4.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  