2009-08-06 09:43:15REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. RETURN AIR TRANSFER GRILLS IN SOME AREAS ARE NOT
 SIZED TO MEET THE EXCEPTIONS UNDER FBC-M 601.4.
 EXAMPLES: DETAIL 1 (COMPUTER/COUNTDOWN/CASH ROOM AREAS)
 AND DETAIL 9 (DEMO ROOM) ON PAGE M2. PLEASE CHECK ALL
 RETURN AIR TRANFER GRILL SIZES FOR COMPLIANCE.
  
 2. PAGE M2: DETAIL 1 SHOWS THE MANUAL PULL STATION FOR
 THE HOOD SUPPRESSION SYSTEM IN EXCESS OF 20 FEET FROM
 THE KITCHEN EXHAUST SYSTEM. ALSO, DETAIL 2 SHOWS A
 MANUAL PULL STATION LESS THAN 10 FEET FROM THE KITCHEN
 EXHAUST SYSTEM. THESE MANUAL ACTUATION DEVICES SHALL BE
 LOCATED AT OR NEAR A MEANS OF EGRESS FROM THE COOKING
 AREA A MINIMUM OF 10 FEET AND A MAXIMUM OF 20 FEET FROM
 THE KITCHEN EXHAUST SYSTEM IN ACCORDANCE WITH FBC-B
 904.11.1.
  
 3. PAGE M2: MECHANICAL KEYNOTE 15.722 CALLS FOR EXHAUST
 FAN INTERLOCK WITH PIZZA OVEN OPERATION. INTERLOCK OF
 EXHAUST FAN WITH ROTISSERIE OPERATION IS ALSO REQUIRED
 IN ACCORDANCE WITH FBC-M 507.2.1.1. THE ACTIVATION OF
 THE EXHAUST FAN SHALL OCCUR THROUGH AN INTERLOCK WITH
 THE COOKING APPLIANCES, BY MEANS OF HEAT SENSORS OR BY
 MEANS OF OTHER APPROVED METHODS.
  
 4. PROVIDE MANUFACTURER'S DATA FOR THE WIND RESISTANT
 CONSTRUCTION AND INSTALLATION OF ALL APPLIANCES EXPOSED
 TO WIND SUCH AS: NEW RTUS, EXHAUST FANS, MUA FANS,
 REMOTE CONDENSERS IN ACCORDANCE WITH FBC-M 301.12.
  
 5. ENERGY CALCULATIONS: THIS JOB CONSTITUTES A
 RENOVATION AS DEFINED IN FBC-B SECTION 13-202. AS SUCH,
 THIS BUILDING SHALL COMPLY WITH METHOD B OF SUBCHAPTER
 13-4 FOR INSULATION, HVAC SYSTEMS, LIGHTING, WATER
 HEATING SYSTEMS AND EXTERIOR ENVELOPE COMPONENTS BEING
 RETROFITTED OR REPLACED IN ACCORDANCE WITH FBC-B
 13-101.1.3. SUBMIT A COMPLETED ENERGY CODE COMPLIANCE
 FORM 400B-08 TO DEMONSTRATE COMPLIANCE WITH THIS
 SECTION. THE FORM 400A-04R WHICH WAS SUBMITTED IS OUT
 OF DATE AND NO LONGER VALID AS OF MARCH 1, 2009, THE
 EFFECTIVE DATE OF THE 2007 FLORIDA BUILDING CODE.
  
 6. A COOLING LOAD CALCULATION FOR ALL NEW AIR
 CONDITIONING APPLIANCES BEING INSTALLED SHALL BE
 ATTACHED TO THE ENERGY CODE COMPLIANCE FORM IN
 ACCORDANCE WITH FBC-B SECTION 13-407.AB.1.
  
 NOTE: SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN
 HOOD EXHAUST AND HOOD SUPPRESSION SYSTEMS.
  