| 2009-08-06 09:43:15 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. RETURN AIR TRANSFER GRILLS IN SOME AREAS ARE NOT |
| | SIZED TO MEET THE EXCEPTIONS UNDER FBC-M 601.4. |
| | EXAMPLES: DETAIL 1 (COMPUTER/COUNTDOWN/CASH ROOM AREAS) |
| | AND DETAIL 9 (DEMO ROOM) ON PAGE M2. PLEASE CHECK ALL |
| | RETURN AIR TRANFER GRILL SIZES FOR COMPLIANCE. |
| | |
| | 2. PAGE M2: DETAIL 1 SHOWS THE MANUAL PULL STATION FOR |
| | THE HOOD SUPPRESSION SYSTEM IN EXCESS OF 20 FEET FROM |
| | THE KITCHEN EXHAUST SYSTEM. ALSO, DETAIL 2 SHOWS A |
| | MANUAL PULL STATION LESS THAN 10 FEET FROM THE KITCHEN |
| | EXHAUST SYSTEM. THESE MANUAL ACTUATION DEVICES SHALL BE |
| | LOCATED AT OR NEAR A MEANS OF EGRESS FROM THE COOKING |
| | AREA A MINIMUM OF 10 FEET AND A MAXIMUM OF 20 FEET FROM |
| | THE KITCHEN EXHAUST SYSTEM IN ACCORDANCE WITH FBC-B |
| | 904.11.1. |
| | |
| | 3. PAGE M2: MECHANICAL KEYNOTE 15.722 CALLS FOR EXHAUST |
| | FAN INTERLOCK WITH PIZZA OVEN OPERATION. INTERLOCK OF |
| | EXHAUST FAN WITH ROTISSERIE OPERATION IS ALSO REQUIRED |
| | IN ACCORDANCE WITH FBC-M 507.2.1.1. THE ACTIVATION OF |
| | THE EXHAUST FAN SHALL OCCUR THROUGH AN INTERLOCK WITH |
| | THE COOKING APPLIANCES, BY MEANS OF HEAT SENSORS OR BY |
| | MEANS OF OTHER APPROVED METHODS. |
| | |
| | 4. PROVIDE MANUFACTURER'S DATA FOR THE WIND RESISTANT |
| | CONSTRUCTION AND INSTALLATION OF ALL APPLIANCES EXPOSED |
| | TO WIND SUCH AS: NEW RTUS, EXHAUST FANS, MUA FANS, |
| | REMOTE CONDENSERS IN ACCORDANCE WITH FBC-M 301.12. |
| | |
| | 5. ENERGY CALCULATIONS: THIS JOB CONSTITUTES A |
| | RENOVATION AS DEFINED IN FBC-B SECTION 13-202. AS SUCH, |
| | THIS BUILDING SHALL COMPLY WITH METHOD B OF SUBCHAPTER |
| | 13-4 FOR INSULATION, HVAC SYSTEMS, LIGHTING, WATER |
| | HEATING SYSTEMS AND EXTERIOR ENVELOPE COMPONENTS BEING |
| | RETROFITTED OR REPLACED IN ACCORDANCE WITH FBC-B |
| | 13-101.1.3. SUBMIT A COMPLETED ENERGY CODE COMPLIANCE |
| | FORM 400B-08 TO DEMONSTRATE COMPLIANCE WITH THIS |
| | SECTION. THE FORM 400A-04R WHICH WAS SUBMITTED IS OUT |
| | OF DATE AND NO LONGER VALID AS OF MARCH 1, 2009, THE |
| | EFFECTIVE DATE OF THE 2007 FLORIDA BUILDING CODE. |
| | |
| | 6. A COOLING LOAD CALCULATION FOR ALL NEW AIR |
| | CONDITIONING APPLIANCES BEING INSTALLED SHALL BE |
| | ATTACHED TO THE ENERGY CODE COMPLIANCE FORM IN |
| | ACCORDANCE WITH FBC-B SECTION 13-407.AB.1. |
| | |
| | NOTE: SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN |
| | HOOD EXHAUST AND HOOD SUPPRESSION SYSTEMS. |
| | |