| 2009-08-19 12:23:54 | 1. MEZZANINE FLOOR AREA TOTAL ON PAGE CS DOES NOT |
| | APPEAR CORRECT. THE TOTAL FLOOR AREA TOTAL AMOUNT MAY |
| | ALSO BE INCORRECT. |
| | |
| | 2. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY |
| | WITH NFPA 241. |
| | |
| | 3. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS |
| | FOR HANDRAILS AND GUARDRAILS. |
| | |
| | 4. DUST WALLS SHOWN ON PAGE D1 SHALL NOT CONSIST OF |
| | NON-RATED VISQUEEN OT OTHER MATERIALS. PLEASE SEE NOTES |
| | ON DUCT WALLS AND DRAPES ON PAGE D1.3. |
| | |
| | 5. IF GASOLINE POWERED SAWS ARE USED, PROPER |
| | CONSIDERATION TO THE PRODUCTION AND ACCUMULATION OF |
| | CARBON MONOXIDE (CO) . PROPER VENTILATION CONTROLS ARE |
| | TO BE UTILIZED TO PREVENT THE PRODUCTION OF CARBON |
| | MONOXIDE WHICH IS A COLORLESS, ODORLESS, AND IN THE |
| | PROPER CONCENTRATION FLAMMABLE. |
| | |
| | 6. IF ANY REQUIRED FIRE PROTECTION SYSTEMS ARE OUT OF |
| | SERVICE MORE THAN FOUR HOURS IN A TWENTY FOUR HOUR |
| | PERIOD A FIRE WATCH WILL BE REQUIRED. ALL FIRE WATCHES |
| | MUST BE APPROVED BY THE BATTALION CHIEF OR HIS DESIGNEE |
| | AND ALL FIRE WATCHES REQUESTS MUST BE IN WRITING. |
| | |
| | 7. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY FIRE |
| | SPRINKLER OR FIRE ALARM SYSTEM REMODELING. |
| | |
| | 8. NEW AUTOMATIC SLIDING DOORS ON PAGE A3 SHALL MEET |
| | THE REQUIREMENTS FOR POWERED OPERATED DOORS. |
| | |
| | 9. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY NEW |
| | HOOD, DUCT, AND FIRE SUPPRESSION SYSTEMS. |
| | |
| | 10. ALL FREEZERS AND COOLER SHALL BE PROTECTED WITH |
| | FIRE SPRINKLER PROTECTION AS SHOWN ON THE SPRINKLER |
| | PLANS. |
| | |
| | 11. NOTES ON PAGE 6025 MENTIONS THE JURISDICTION OF |
| | PORT CHARLOTTE, FLORIDA. WRONG LOCATION. |
| | |
| | 12. PLEASE PROVIDE FLAME SPREAD REQUIREMENTS FOR NEW |
| | CEILING TILES PLANNED FOR THE LOCATION. |
| | |
| | 13. ALL WORK IS SUBJECT TO FIELD INSPECTION AND |
| | APPROVAL. |
| | |
| | |
| | MIKE CARSILLO, BATTALION CHIEF |
| | BUREAU OF FIRE PREVENTION |
| | |