Plan Review Notes
Plan Review Notes For Permit 09070775
Permit Number 09070775
Review Stop E
Sequence Number 1
Notes
Date Text
2009-08-26 09:15:45 
 ** DENIED REVIEW **
  
  
  
 1) NOTE: THE SEAL IN USE OF STRUCTURAL PLANS IS NO
 LONGER VALID FOR USE IN THE STATE OF FLORIDA. PLEASE
 SEE RULING UNDER FLORIDA ADMINISTRATIVE CODE
 61G15-23.001. THIS SECTION WAS REVISED IN FEBRUARY OF
 2004 THAT THE WORDING OF *CERTIFICATE* ON SAID SEAL IS
 NO LONGER PERMITTED. THE NEW WORDING OF *LICENSE* WAS
 REQUIRED. ALL SEALS WERE REQUIRED TO BE REVISED/NEW. AN
 EXTENSION WAS GRANTED BY THE BOARD OF ENGINEERS TO THE
 DATE OF DECEMBER 31ST 2005. HOWEVER AFTER THAT DATE THE
 OLD SEALS COULD NOT LONGER BE USED.
 THIS COMMENT IS REQUIRED WHETHER OR NOT COMMENT IS MADE
 BY ANY OTHER TRADE.
  
  
 2) NOTE: THE SUBMITTED ENERGY CALCULATIONS ARE NOT CODE
 COMPLIANT.
 THE VERSION SUBMITTED IS FROM THE 2004 FLORIDA BUILDING
 CODE. PLEASE KNOW THAT ALL PERMIT APPLICATIONS
 SUBMITTED AFTER MARCH 1ST 2009 SHALL BE UNDER THE 2007
 FBC W/ 2009 REVISIONS.
 PLEASE SEE 13-400.3.A, 13-400.3.B.
 AS THIS IS NOT A WHOLE BUILDING PLEASE SEE
 13-400.0.B.4, 13-415.AB.5, 13-415.B.1 FOR LIGHTING
 PERFORMANCE CALCULATIONS FOR PRESCRIPTIVE REQUIREMENTS.
  
 MAY NOT SUBMIT AND USE AND METHOD *A* WHOLE BUILDING
 CALCULATION UNLESS IT IS A WHOLE BUILDING WITHIN THE
 SCOPE.
 PLEASE ALSO SEE THAT NO INPUT DATA REPORT WAS
 SUBMITTED. IN ORDER TO VERIFY CODE COMPLIANCE FOR THE
 INFORMATION ON PLANS COORDINATING WITH THE SUBMITTED
 CALCULATIONS, THE INPUT DATA REPORT MUST ACCOMPANY THE
 SUBMITTED SUMMARY SHEETS OF THE CALCULATIONS.
  
 ** IMPORTANT, PLEASE BE SURE ALL INFORMATION ON THE
 IDR, IS COORDINATED WITH PLANS.
  
 ** IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 3) NOTE: PLEASE SUBMIT PHOTO-METRICS FOR STAIR EGRESS
 AREAS. PLEASE SEE NFPA-101 7.8.1.3, 7.9.1.2 AND 7.9.2.2
 OF THE LIFE SAFETY CODE. REQUIRES A MINIMUM OF 10FT
 CANDLES UNDER NORMAL AND IS PERMITTED TO GO DOWN TO 1FT
 CANDLE UNDER EMERGENCY. THIS INCLUDES OUTSIDE EGRESS
 STAIRS.
 PLEASE SEE NFPA-70 700.12 FOR ACCEPTABLE BACK UP AND
 CIRCUITING PER 700.12F. CHAPTER 10 OF THE FBC ALSO
 GOVERNS EGRESS ILLUMINATION.
  
 4) NOTE: ANY NEW LIGHTING CONTROLS ARE REQUIRED TO MEET
 PRESCRIPTIVE REQUIREMENTS OF 13-415.AB.1.1,.1.2, .1.3
 AND .1.4.
 EXAMPLE: INTERIOR JANITOR CLOSET INDICATING ONLY A
 STANDARD WALL SWITCH.
 EXAMPLE: OUTSIDE LIGHTS NEEDING TO MEET ONE OF TWO
 MINIMUM REQUIRED METHODS.
 EXAMPLE: RECEIVING AREA. WHERE ARE THE EXISTING
 LIGHTING CONTROLS FOR SEPARATE SPACES? IF NEW, THEN
 MUST MEET REQUIREMENTS FOR SEPARATE SPACES. IF NOT NEW
 THEN PLEASE SHOW THE EXISTING.
 EXAMPLE: MEAT COOLER, PRODUCE COOLER ETC.
  
 ** ALL LOCATIONS AND SEPARATE SPACES ARE REQUIRED TO
 MEET MINIMUM PRESCRIPTIVE REQUIREMENTS FOR AUTOMATED
 LIGHTING CONTROLS.
  
 5) NOTE: SHEET E-2 STATES A NOTE #9 FOR A ROOM LOCATED
 ON THE EAST SIDE OF THE BUILDING WHICH STATES *
 REMODELED ELECTRICAL*. HOWEVER NO INFORMATION COULD BE
 LOCATED.
 ALL OF THE OTHER AREAS ARE NOTED TO OTHER SHEETS AND
 ENLARGED DETAILS HOWEVER THIS ROOM/LOCATION COULD NOT
 BE FOUND.
 PLEASE EXPLAIN.
 AS THE SCOPE IS NOT CLEAR IT IS NOT POSSIBLE TO REVIEW.
  
 6) NOTE: PLEASE SEE 210.8B2 FOR THE 2005 NEC. ALL
 15/20AMP RECEPTACLES LOCATED IN KITCHEN AREAS SHALL BE
 GFI/GFI PROTECTED. THIS IS REQUIRED WHETHER OR NOT
 THESE ARE FEEDING COUNTER SPACES.
  
 8) NOTE: PLEASE SHOW ALL CLASS AND DIVISION LOCATIONS
 PER NEC 500.
  
 9) NOTE: PLEASE INDICATE IF THE CONTINUOUS LOADS ARE
 ALREADY FIGURED AT 125% ALONG WITH LARGEST MOTORS LOADS
 OR CONTINUOUS MOTOR LOADS.
 EXAMPLE: LIGHTING, STORAGE TYPE WATER HEATERS, ETC.
 PLEASE ALSO PROVIDE INFORMATION ON AIR CURTAIN MOTORS.
 ARE THESE CONTROLLED FOR OPERATION DURING THE DOOR
 OPENING OR CONTINUOUS DURING THE HOURS OF STORE
 OPERATION/OPEN HOURS?
 215.3, 230.42
  
 10) NOTE: THE NOTE ON RISER SHEET 16.R64 INDICATES
 THERE IS AN ISSUE WITH THE RATING OF THE BREAKERS BEING
 EXCEEDED BY THE AVAILABLE FAULT CURRENT. PLEASE VERIFY
 THIS AT THIS TIME. PLEASE KNOW THAT IF THIS IS INDEED
 THE CASE A SEPARATE ELECTRICAL PERMIT SHOULD BE APPLIED
 FOR AS SOON AS POSSIBLE TO ADDRESS THIS ISSUE. MINIMUM
 CODE COMPLIANCE FOR SAFETY OF THESE ISSUES INCLUDING
 ANY FIRE HAZARDS NEEDS TO BE ADDRESSED.
 110.9.
  
 ** PERMIT HAS BEEN APPLIED FOR HOWEVER NOT BY ANY
 LICENSED CONTRACTOR. PERMIT MAY NOT BE ISSUED UNTIL
 LICENSED CONTRACTOR HAS APPLIED UNDER THIS PERMIT
 NUMBER.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  