| 2009-08-26 09:15:45 | |
| | ** DENIED REVIEW ** |
| | |
| | |
| | |
| | 1) NOTE: THE SEAL IN USE OF STRUCTURAL PLANS IS NO |
| | LONGER VALID FOR USE IN THE STATE OF FLORIDA. PLEASE |
| | SEE RULING UNDER FLORIDA ADMINISTRATIVE CODE |
| | 61G15-23.001. THIS SECTION WAS REVISED IN FEBRUARY OF |
| | 2004 THAT THE WORDING OF *CERTIFICATE* ON SAID SEAL IS |
| | NO LONGER PERMITTED. THE NEW WORDING OF *LICENSE* WAS |
| | REQUIRED. ALL SEALS WERE REQUIRED TO BE REVISED/NEW. AN |
| | EXTENSION WAS GRANTED BY THE BOARD OF ENGINEERS TO THE |
| | DATE OF DECEMBER 31ST 2005. HOWEVER AFTER THAT DATE THE |
| | OLD SEALS COULD NOT LONGER BE USED. |
| | THIS COMMENT IS REQUIRED WHETHER OR NOT COMMENT IS MADE |
| | BY ANY OTHER TRADE. |
| | |
| | |
| | 2) NOTE: THE SUBMITTED ENERGY CALCULATIONS ARE NOT CODE |
| | COMPLIANT. |
| | THE VERSION SUBMITTED IS FROM THE 2004 FLORIDA BUILDING |
| | CODE. PLEASE KNOW THAT ALL PERMIT APPLICATIONS |
| | SUBMITTED AFTER MARCH 1ST 2009 SHALL BE UNDER THE 2007 |
| | FBC W/ 2009 REVISIONS. |
| | PLEASE SEE 13-400.3.A, 13-400.3.B. |
| | AS THIS IS NOT A WHOLE BUILDING PLEASE SEE |
| | 13-400.0.B.4, 13-415.AB.5, 13-415.B.1 FOR LIGHTING |
| | PERFORMANCE CALCULATIONS FOR PRESCRIPTIVE REQUIREMENTS. |
| | |
| | MAY NOT SUBMIT AND USE AND METHOD *A* WHOLE BUILDING |
| | CALCULATION UNLESS IT IS A WHOLE BUILDING WITHIN THE |
| | SCOPE. |
| | PLEASE ALSO SEE THAT NO INPUT DATA REPORT WAS |
| | SUBMITTED. IN ORDER TO VERIFY CODE COMPLIANCE FOR THE |
| | INFORMATION ON PLANS COORDINATING WITH THE SUBMITTED |
| | CALCULATIONS, THE INPUT DATA REPORT MUST ACCOMPANY THE |
| | SUBMITTED SUMMARY SHEETS OF THE CALCULATIONS. |
| | |
| | ** IMPORTANT, PLEASE BE SURE ALL INFORMATION ON THE |
| | IDR, IS COORDINATED WITH PLANS. |
| | |
| | ** IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| | |
| | 3) NOTE: PLEASE SUBMIT PHOTO-METRICS FOR STAIR EGRESS |
| | AREAS. PLEASE SEE NFPA-101 7.8.1.3, 7.9.1.2 AND 7.9.2.2 |
| | OF THE LIFE SAFETY CODE. REQUIRES A MINIMUM OF 10FT |
| | CANDLES UNDER NORMAL AND IS PERMITTED TO GO DOWN TO 1FT |
| | CANDLE UNDER EMERGENCY. THIS INCLUDES OUTSIDE EGRESS |
| | STAIRS. |
| | PLEASE SEE NFPA-70 700.12 FOR ACCEPTABLE BACK UP AND |
| | CIRCUITING PER 700.12F. CHAPTER 10 OF THE FBC ALSO |
| | GOVERNS EGRESS ILLUMINATION. |
| | |
| | 4) NOTE: ANY NEW LIGHTING CONTROLS ARE REQUIRED TO MEET |
| | PRESCRIPTIVE REQUIREMENTS OF 13-415.AB.1.1,.1.2, .1.3 |
| | AND .1.4. |
| | EXAMPLE: INTERIOR JANITOR CLOSET INDICATING ONLY A |
| | STANDARD WALL SWITCH. |
| | EXAMPLE: OUTSIDE LIGHTS NEEDING TO MEET ONE OF TWO |
| | MINIMUM REQUIRED METHODS. |
| | EXAMPLE: RECEIVING AREA. WHERE ARE THE EXISTING |
| | LIGHTING CONTROLS FOR SEPARATE SPACES? IF NEW, THEN |
| | MUST MEET REQUIREMENTS FOR SEPARATE SPACES. IF NOT NEW |
| | THEN PLEASE SHOW THE EXISTING. |
| | EXAMPLE: MEAT COOLER, PRODUCE COOLER ETC. |
| | |
| | ** ALL LOCATIONS AND SEPARATE SPACES ARE REQUIRED TO |
| | MEET MINIMUM PRESCRIPTIVE REQUIREMENTS FOR AUTOMATED |
| | LIGHTING CONTROLS. |
| | |
| | 5) NOTE: SHEET E-2 STATES A NOTE #9 FOR A ROOM LOCATED |
| | ON THE EAST SIDE OF THE BUILDING WHICH STATES * |
| | REMODELED ELECTRICAL*. HOWEVER NO INFORMATION COULD BE |
| | LOCATED. |
| | ALL OF THE OTHER AREAS ARE NOTED TO OTHER SHEETS AND |
| | ENLARGED DETAILS HOWEVER THIS ROOM/LOCATION COULD NOT |
| | BE FOUND. |
| | PLEASE EXPLAIN. |
| | AS THE SCOPE IS NOT CLEAR IT IS NOT POSSIBLE TO REVIEW. |
| | |
| | 6) NOTE: PLEASE SEE 210.8B2 FOR THE 2005 NEC. ALL |
| | 15/20AMP RECEPTACLES LOCATED IN KITCHEN AREAS SHALL BE |
| | GFI/GFI PROTECTED. THIS IS REQUIRED WHETHER OR NOT |
| | THESE ARE FEEDING COUNTER SPACES. |
| | |
| | 8) NOTE: PLEASE SHOW ALL CLASS AND DIVISION LOCATIONS |
| | PER NEC 500. |
| | |
| | 9) NOTE: PLEASE INDICATE IF THE CONTINUOUS LOADS ARE |
| | ALREADY FIGURED AT 125% ALONG WITH LARGEST MOTORS LOADS |
| | OR CONTINUOUS MOTOR LOADS. |
| | EXAMPLE: LIGHTING, STORAGE TYPE WATER HEATERS, ETC. |
| | PLEASE ALSO PROVIDE INFORMATION ON AIR CURTAIN MOTORS. |
| | ARE THESE CONTROLLED FOR OPERATION DURING THE DOOR |
| | OPENING OR CONTINUOUS DURING THE HOURS OF STORE |
| | OPERATION/OPEN HOURS? |
| | 215.3, 230.42 |
| | |
| | 10) NOTE: THE NOTE ON RISER SHEET 16.R64 INDICATES |
| | THERE IS AN ISSUE WITH THE RATING OF THE BREAKERS BEING |
| | EXCEEDED BY THE AVAILABLE FAULT CURRENT. PLEASE VERIFY |
| | THIS AT THIS TIME. PLEASE KNOW THAT IF THIS IS INDEED |
| | THE CASE A SEPARATE ELECTRICAL PERMIT SHOULD BE APPLIED |
| | FOR AS SOON AS POSSIBLE TO ADDRESS THIS ISSUE. MINIMUM |
| | CODE COMPLIANCE FOR SAFETY OF THESE ISSUES INCLUDING |
| | ANY FIRE HAZARDS NEEDS TO BE ADDRESSED. |
| | 110.9. |
| | |
| | ** PERMIT HAS BEEN APPLIED FOR HOWEVER NOT BY ANY |
| | LICENSED CONTRACTOR. PERMIT MAY NOT BE ISSUED UNTIL |
| | LICENSED CONTRACTOR HAS APPLIED UNDER THIS PERMIT |
| | NUMBER. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |