2009-08-11 16:52:52BUILDING PLAN REVIEW
 PERMIT: 09070775
 ADD: 4295 45TH ST
 CONT: TO BE DETERMINED
 TEL: (561)856-6655 NEYITA LEIVA
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 AUGUST 11/2009
 1ST REVIEW
 ACTION: DENIED
  
 1A) COVER SHEET/ CODES: PLANS SUBMITTED FOR PERMIT
 (FIRST TIME REVIEW) AFTER MARCH 1ST, 2009 SHALL BE
 REVIEWED TO THE 2007 FBC BUILDING WITH 2009
 SUPPLEMENTS.
 PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING
 BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO
 WHAT LEVEL ALTERATION WILL BE COMPLETED UNDERTHIS
 PERMIT.
 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE.
  
 1B) COVER SHEET/ CODES: PLANS INDICATE THE HANDICAPPED
 ACCESSIBILITY GUIDELINES AS AMERICANS WITH DISSIBILITY
 GUIDELINES PLEASE SEE FLORIDA'S BUILDING CODE , CHAPTER
 11 WHICH NOT ONLY ADOPTED THE ADAG BUT IS MORE
 RESTRICTIVE AND WERE ADOPTED BY THE DEPARTMENT OF
 JUSTICE.
  
 2) SUBMITTED WAS THE 2004 ENERGY CALCS FORM 400A-2004R.
 THIS FORM IS NO LONGER IN EFFECT. WHEN THE 2007 FBC
 CAME INTO EFFECT THIS FORM WAS NULL IN VOID. PLEASE
 REVIEW AND USE FORM 400B-08, THIS IS FOR COMMERCIAL
 RENOVASIONS.
  
 3) SHEET S0:
  
 3A) SECTION # 5 DEALS WITH FOUNDATIONS PLEASE PROVIDE
 THE SOILS REPORT PREPARED BY ECS OF FLORIDA LLC, JULY
 9/ 2009. 1802.2.1 QUESTIONABLE SOIL. WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6 .
  
 3B) SECTION # 2 & 6 BOTH MAKE REFRENECE TO THE IBC
 SPECIAL INSPECTION SECTION 1704, PLEASE REVIEW THIS
 SECTION WAS NOT ADOPTED INTO THE FLORIDA BUILDING CODE,
 BUILDING.
  
 4) THE COVERSHEET INDICATES SQUARE FOOTAGE BY OCCUPANCY
 BUT NOT BY EXISTING AND ADDITIONAL SQ. FOOTAGE BEING
 ADDED AS AN ADDITION. 106.1.2. ADDITIONAL INFORMATION
 REQUIRED.
  
 5) ADDITION IS LOCATED WITHIN A FLOODZONE A8 AT WITH A
 REQUIRED ELEVATION OF 15.5 FT NGVD, FBC BUILDING
 3110.1.2 / CITY OF WPB CODE OF ORDINANCES SECTION
 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A
 FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED.
  
 6) PLEASE NOTE THAT PRODUCT APPROVALS WILL NOT BE
 REQUIRED AT TIME OF PERMITTING BUT WILL BE REQUIRED FOR
 FULL REVIEW.
  
 BUILDING PROVISO:FL BLD CODE 1609.6.2.2 COMPONENTS &
 CLADDING, PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT
 INSPECTOR OF PRODUCT TESTING REPORTS, MISSING REPORTS
 ARE AS FOLLOWS:
 A) EXTERIOR GLAZED WINDOWS
 B) MULLION
 C) EXTERIOR GLAZED DOORS, AUTOMATIC SLIDDING GLASS
 DOORS W/ TRANSOM
 D) OVERHEAD DOORS
 E) WALL LOUVERS
 F) EFIS SYSTEMS
 G) ROOFING ASSEMBLIES INCLUDING ROOF INSULATION
 H) PERMANUFACTURED A/C STANDS
  
 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 7) A3.3 PLEASE NOTE THAT ROOF TOP MECHANICAL EQUIPMENT
 MUSST MEET THE WIND REQUIREMENTS IN CHAPTER 16 OF FBC.
 301.13 FBC MECHANICAL. WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST WIND
 PRESSURES ON THE EQUIPMENT AND THE SUPPORTS AS
 DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, BUILDING. NOTE THE STRUCTURAL SHEETS INDICATE THE
 CURB ATTACHMENTS TO THE ROOF DECK BUT NOT THE UNIT TO
 THE ROOF CURB.
  
 8) A3.4 PLEASE SEE A3.4 EXTERIOR WALL SECTION INDICATE
 1/2 INCH CD PLYWOOD ON WALLS. PLEASE SEE SECTION
 603.1(1.1)AND (1.2) FOR WHERE FIRE RETARDANT TREATED
 ELEMENTS CAN BE INSTALLED.
  
 9) PLANS INDICATE THE USE OF WALK IN COOLERS PLEASE
 PROVIDE DOCUMENTATION THAT THE THERMA- STRUCTURE
 COOLERS COMPLIES WITH SECTION 2603.4.1.2 (1-4).
  
 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.