Plan Review Notes
Plan Review Notes For Permit 09070747
Permit Number 09070747
Review Stop E
Sequence Number 1
Notes
Date Text
2009-08-02 12:15:59** DENIED REVIEW **
  
  
  
 1) NOTE: PLANS STATE TO REPLACE LIGHTING FIXTURES WITH
 NEW. PLANS ALSO STATES TO COMPLY WITH FBC CHAPTER 13
 HOWEVER NO INFORMATION IS BEING SUBMITTED OR SHOWN FOR
 MINIMUM CODE COMPLIANCE.
 PLEASE SEE FBC 13-415.AB.5, 13-415.B.2 FOR PRESCRIPTIVE
 MINIMUMS FOR LIGHTING BEING CHANGED. PLEASE SUBMIT FLA
 COM LIGHTING PERFORMANCE CALCULATIONS FOR NEW BEING
 INSTALLED. PLEASE KEEP IN MIND ANY OTHER LIGHTING IN
 ROOMS OR LOCATIONS WOULD ALSO NEED TO BE INCLUDED. THE
 REVISED CHAPTER 13 DOES NOT GIVE ALLOWANCES FOR ACCENT,
 DECRETIVE LIGHTING UNDER THE NEW CODE.
  
  
  
 2) NOTE: PLANS STATE THE ELECTRICAL WORK SHALL BE DONE
 TO THE LATEST EDITION OF THE ELECTRICAL CODE, HOWEVER
 THE LATEST EDITION OF THE ELECTRICAL CODE HAS NOT BEEN
 ADOPTED BY THE STATE OF FLORIDA.
 CURRENTLY THE STATE OF FLORIDA IS UNDER 2005 NFPA-70.
 PLANS ALSO STATE TO COMPLY WITH THE 2007 FBC CHAPTER
 13, HOWEVER CHAPTER 13 WAS COMPLETELY REVISED UNDER THE
 2009 GLITCH AMENDMENTS. THERE WERE SUBSTANTIAL CHANGES.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  