| Plan Review Notes For Permit 09070747 |
| Permit Number |
09070747 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-08-02 12:15:59 | ** DENIED REVIEW ** | | | | | | | | | | | | 1) NOTE: PLANS STATE TO REPLACE LIGHTING FIXTURES WITH | | | NEW. PLANS ALSO STATES TO COMPLY WITH FBC CHAPTER 13 | | | HOWEVER NO INFORMATION IS BEING SUBMITTED OR SHOWN FOR | | | MINIMUM CODE COMPLIANCE. | | | PLEASE SEE FBC 13-415.AB.5, 13-415.B.2 FOR PRESCRIPTIVE | | | MINIMUMS FOR LIGHTING BEING CHANGED. PLEASE SUBMIT FLA | | | COM LIGHTING PERFORMANCE CALCULATIONS FOR NEW BEING | | | INSTALLED. PLEASE KEEP IN MIND ANY OTHER LIGHTING IN | | | ROOMS OR LOCATIONS WOULD ALSO NEED TO BE INCLUDED. THE | | | REVISED CHAPTER 13 DOES NOT GIVE ALLOWANCES FOR ACCENT, | | | DECRETIVE LIGHTING UNDER THE NEW CODE. | | | | | | | | | | | | 2) NOTE: PLANS STATE THE ELECTRICAL WORK SHALL BE DONE | | | TO THE LATEST EDITION OF THE ELECTRICAL CODE, HOWEVER | | | THE LATEST EDITION OF THE ELECTRICAL CODE HAS NOT BEEN | | | ADOPTED BY THE STATE OF FLORIDA. | | | CURRENTLY THE STATE OF FLORIDA IS UNDER 2005 NFPA-70. | | | PLANS ALSO STATE TO COMPLY WITH THE 2007 FBC CHAPTER | | | 13, HOWEVER CHAPTER 13 WAS COMPLETELY REVISED UNDER THE | | | 2009 GLITCH AMENDMENTS. THERE WERE SUBSTANTIAL CHANGES. | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|