2009-08-14 11:09:54*****DENIED*****
  
 THE FOLLOWING COMMENTS BASED UPON THE FIRE REVIEW
 CONDUCTED BY BATTALION CHIEF/FIRE MARSHAL MIKE
 CARSILLO, PH. # 561-804-4724:
  
 1. NO SURVEY PROVIDED WITH DRAWINGS.
  
 2. NO WARNING LABELS DISPLAYED FOR THE TANK. PLEASE
 PROVIDE PRODUCT LABELS, "NO SMOKING", AND NFPA 704
 PLACARDS FOR THE TANK.
  
 3. EXTREME CARE IS TO BE TAKEN WHEN DEGGS AND CLEANING
 EXISTING UNDERGROUND FUEL TANK. UNDERGROUND FUEL TANK
 IS CONSIDERED TO BE A CONFINED SPACE.
  
 4. WHAT DOES THE GENERATOR SUPPLY POWER TO, FOR WHICH
 THE FUEL SUPPLY IS NECESSARY.
  
 5. PLEASE PROVIDE PRODUCT SUBMITTALS FOR THE ABOVE
 GROUND FUEL TANK BEING PROPOSED.
  
 6. TANK INSTALLATION TO COMPLY WITH NFPA 30 AND 30A.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  