| Plan Review Notes For Permit 09070734 |
| Permit Number |
09070734 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-08-14 11:09:54 | *****DENIED***** | | | | | | THE FOLLOWING COMMENTS BASED UPON THE FIRE REVIEW | | | CONDUCTED BY BATTALION CHIEF/FIRE MARSHAL MIKE | | | CARSILLO, PH. # 561-804-4724: | | | | | | 1. NO SURVEY PROVIDED WITH DRAWINGS. | | | | | | 2. NO WARNING LABELS DISPLAYED FOR THE TANK. PLEASE | | | PROVIDE PRODUCT LABELS, "NO SMOKING", AND NFPA 704 | | | PLACARDS FOR THE TANK. | | | | | | 3. EXTREME CARE IS TO BE TAKEN WHEN DEGGS AND CLEANING | | | EXISTING UNDERGROUND FUEL TANK. UNDERGROUND FUEL TANK | | | IS CONSIDERED TO BE A CONFINED SPACE. | | | | | | 4. WHAT DOES THE GENERATOR SUPPLY POWER TO, FOR WHICH | | | THE FUEL SUPPLY IS NECESSARY. | | | | | | 5. PLEASE PROVIDE PRODUCT SUBMITTALS FOR THE ABOVE | | | GROUND FUEL TANK BEING PROPOSED. | | | | | | 6. TANK INSTALLATION TO COMPLY WITH NFPA 30 AND 30A. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|