Plan Review Notes
Plan Review Notes For Permit 09070711
Permit Number 09070711
Review Stop B
Sequence Number 2
Notes
Date Text
2009-09-23 11:47:32CHANGE OF CONTRACTOR NO PRODUCT APPROVALS WERE
 SUBMITTED, CALLED ROSE KENNEY WILL REQUIRE 2 SETS OF
 ALL PRODUCT APPROVALS.\
  
  
 BUILDING PLAN REVIEW
 PERMIT: 09070711
 ADD: 2401 SPRUCE AVE
 CONT: CLEARSPAN STRUCTURES
 TEL: (561)662-1819 ROSE KENNEY
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION REVIEW # 4 DATED 9-11-09
 ACTION: DENIED
  
 1) THE COVER SHEET OR INDEX SHEET INDICATES THERE TO BE
 A NEW LS-1 SHEET, MISSING.
  
 2) PLEASE INDICATE THE WALL OR CEILING MOUNTED
 DIRECTIONAL AND EXIT SIGNAGE, THE SIGNAGE ON SHEET A-1
 IS NOT CLEAR IN WHICH CORRIDOR THE OCCUPANT LOAD IS
 BEING DIRECTED. 1006.3.8.
  
 3A) SHEET A-1, A-3, A-7 & A-8 ALL INDICATE A NEW STAIR
 & LANDING AT DOOR# 104. THE DETAIL D3 / SHEET A-7
 INDICATES THE LANDING BEING 3'-8" IN LENGTH SECTION
 1009.4 INDICATES THE MINIMUM LENGTH IN THE DIRECTION OF
 TRAVEL OF 48".
  
 3B) THIS SAME STAIRAND LANDING APPEAR TO CROSS THE
 PROPERTY LINE OR AS INDICATED ON THE PLANS THEY ARE
 JUSST CUT OFF, THE TOP CORNER OF THE LANDING AND
 PORTION OF STEP. 101.3* THE OTHER ISSUE EACH STEP SHALL
 BE READILY VISIBLE. 1003.5.1.
  
 4) SHEET A-4 INDICATES WINDOWS WITH THE USE OF GLASS
 BLOCK PLEASE PROVIDE PRODUCT APPROVALS FOR LARGE
 MISSILE TESTED GLASS BLOCKRULE 9B-72 AND 1609.1.
  
 5) A-5 THE COMMENTARY SHEET SUPPLIED FOR THE REVISIONS
 INDICATES ON A-5 ABOVE THE TECHNICAL SUPPORRT PLATFORM
 THE METAL RAILING WAS ELININATED AND A NEW DRYWALL
 PARTITION WILL TAKE ITS PLACE PLEASE REVIEW SECTION 6
 IT STILL APPEARS TO BE THERE. DISCREPANCY, 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 6) SHEET A-6 INDICATES A DOORWAY WITH NEW TRANSOM,
 PLEASE SUBMIT NEW PRODUCT APPROVALS, IT IS UNCLEAR IF
 THIS WAS TESTED AS A SINGLE UNIT OR IF 3 PRODUCT
 APPROVALS WILL BE REQUIRED. (1) DOOR, (2) HORIZONTAL
 MULLION & (3) STOREFRONT GLAZED WINDOW UNIT , RULE
 9B-72 & 1609.1.
  
 7) SHEET A-12 NOTE BOTTOM LEFT CORNER OF PLANS
 INDICATES THE FINAL FINISHES TO BE CONFIRMED WITH CCE.
 PLEASE PROVIDE THE MINIMUM CRITICAL RADIENT FLUX FOR
 CARPETS FOR THE A & B OCCUPANCIES 804.5.1. BEFORE FLOOR
 FINISHES ARE INSTALLED.
  
 8) A-14 PLEASE REMOVE NOTES INDICATING THE RESIDENTIAL
 CODE.
  
 9A) PRODUCT APPROVALS THAT WERE LISTED ABOVE WILL ALSO
 NEED TO BE REVIEWED BY THE DESIGNER OF RECORD AND AFFIX
 THEIR SHOP DRAWING STAMP. 106.3.3 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITTING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 9B) PLEASE NOTE IF OTHER PRODUCT APPROVALS ARE TO BE
 INSTALLED UNDER THIS PERMIT NOT MENTIONED ABOVE BUT ARE
 SUBJECT TO RULE 9B-72 THEY WILL ALSO NEED TO BE
 SUBMITTED FOR REVIEW.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  