| Plan Review Notes For Permit 09070711 |
| Permit Number |
09070711 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-10-08 15:27:21 | *****DENIED***** | | | | | | | | | 1. THE ACTUAL PROJECT ADDRESS SHALL BE IN THE TITLE | | | BLOCK OF EACH SUBMITTED PLAN SHEET. THE ADDRESS OF 425 | | | 24TH STREET IS CURRENTLY SHOWN IN THE PLANS. | | | | | | 2. AS PER 12/31/2008, NFPA 101, LIFE SAFETY CODE, 2006 | | | EDITION SHALL BE REFERENCED. THE 2003 EDITION IS LISTED | | | IN THE APPLICABLE CODE SECTION ON SHEET SP-1 (COVER | | | PAGE). | | | | | | 3. UNABLE TO LOCATE THE LIFE SAFETY PLAN (LS-1) IN THE | | | PLAN PACKAGE AS INDICATED ON THE COVER SHEET (SP-1). | | | | | | 4. ON THE APPROPITE EXTERIOR ELEVATION WHICH FRONTS THE | | | STREET, DISPLAY/SHOW THE NUMERICAL ADDRESS OF THE | | | PROPERTY. | | | | | | 5. DISPLAY/SHOW THE LOCATION OF THE REQUIRED KNOX BOX. | | | | | | 6. SPECIFY THE INTERIOR FINISH MATERIALS FOR THE WALLS | | | AND CEILINGS IN TERMS OF CLASS A. CLASS B, OR CLASS C. | | | | | | 7. SHOW THE LOCATION OF THE 2A10:BC RATED FIRE | | | EXTINGUISHERS WHICH SATISFY THE 75' TRAVEL DISTANCE. | | | | | | 8. PROVIDE A LAYOUT OF THE PROPOSED FIRE SPRINKLER | | | HEADS. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|