Plan Review Notes
Plan Review Notes For Permit 09070711
Permit Number 09070711
Review Stop E
Sequence Number 1
Notes
Date Text
2009-10-09 10:51:25 
  
 ** DENIED **
  
 1) NOTE: THE SUBMITTED PLANS CONTAIN THE OLD ADDRESS
 UNDER THE PREVIOUS EXPIRED PERMIT OF 425 24TH ST.
 HOWEVER PLANS ARE NOW SUBMITTED UNDER A NEW PERMIT WITH
 AN APPLIED LOCATION OF 2401 SPRUCE AVE.
 PLEASE COORDINATE THE ACTUAL APPLIED LOCATION WITH
 PLANS.
  
 2) NOTE: THE SUBMITTED ENERGY CALCULATIONS DO NOT
 COORDINATED FOR ELECTRICAL AS WELL AS OTHER TRADES.
 PLEASE SEE COMMENTS FROM OTHER TRADES SUCH AS BUILDING
 FOR FLOOR TYPES WHICH ARE ALL SHOWN AS CARPET AND
 RUBBER PADDING.
 THE INPUT DATA REPORT INDICATES EXTERIOR LIGHTING WHICH
 IS EXEMPT BASED ON THE ENERGY CODE. HOWEVER NO
 LOCATIONS ON THIS BUILDING ARE HISTORIC LANDMARK OR
 MONUMENT. NO LOCATIONS ARE REQUIRED BY STATUTE, HEALTH,
 LIFE SAFETY ORDINANCE ETC.
 THE MANUAL ON/OFF IS NOT ACCURATE BASED ON THE REQUIRED
 AUTOMATED CONTROLS.
 13-415.2.ABC.1.3,13-415.2, 13-415.1.AB.1
  
 3) NOTE: PLEASE COMPLETE LIGHTING CONTROLS PER FBC
 13-415.1.ABC.1.1,.1.2,.1.3, .1.4.
 PLEASE SEE ROOMS SUCH AS STORAGE ROOM, CHAIR STORAGE,
 MULTI-PURPOSE STORAGE, HALLWAYS ALL SHOW STANDARD
 CONTROL DEVICES WITHOUT AUTOMATED CONTROLS OF SOME
 KIND.
 PLEASE REVISE PLANS AND PROVIDE DETAILS FOR THESE
 AREAS. MOST OTHER AREAS ARE STILL SHOWING MOTION
 SENSORS. PLEASE VERIFY IF THESE ARE IN FACT MOTION
 SENSORS OR OCCUPANCY SENSORS?
 PLEASE ALSO KNOW THAT DEVICES IN MULTI-GANG BATHROOMS
 ARE REQUIRED TO BE DUAL TECHNOLOGY.
  
 4) NOTE: PLEASE SEE RISER AND PANEL DP2 WHICH INDICATES
 A 400AMP BREAKER FEEDING PANEL E YET THE RISER
 INDICATES 350MCM WHICH IS NOT RATED FOR THE 400AMP OVER
 CURRENT PROTECTION SHOWN.
 310.16,110.14,240.4
  
 5) NOTE: PLEASE CONFIRM AIC RATINGS FOR ALL SERVICE
 EQUIPMENT. PLANS AND PANEL SCHEDULES STATE 42K FOR ALL
 PANELS AND BREAKERS. IF 42K RATED PANELS ARE USED FOR
 ALL PANELS AND BREAKERS THIS WOULD BE A SUBSTANTIAL
 EXPENSE. THIS IS OK HOWEVER IF ALL IS SHOWN AT 42K,
 THEN ALL PANELS AND BRANCH BREAKERS WILL BE REQUIRED TO
 BE INSTALLED PER PLANS.
 110.9
  
 **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  