| 2009-10-05 16:18:02 | BUILDING PLAN REVIEW |
| | PERMIT: 09070635 |
| | ADD: 1600 N DIXIE HWY |
| | CONT: O/B CIOFFI, JOHN & GILDA |
| | TEL: (561)310-6252 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| | MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC |
| | BUILDING WITH 2009 SUPPLEMENTS. |
| | |
| | PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING |
| | BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO |
| | WHAT LEVEL ALTERATION WILL BE COMPLETED UNDER THIS |
| | PERMIT. 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST |
| | ELECT ONE OR A COMBINATION OF LEVELS OF ALTERATION |
| | PURSUANT TO SECTIONS 403, 404 AND 405 OF THIS CODE, IN |
| | THIS CASE CHANGE OF OCCUPANCY CHAPTER 9. |
| | |
| | 2) EXISTING BUILDING CODE 904.1 GENERAL. FIRE |
| | PROTECTION REQUIREMENTS OF SECTION 912 SHALL APPLY |
| | WHERE A BUILDING OR PORTIONS THEREOF UNDERGO A CHANGE |
| | OF OCCUPANCY CLASSIFICATION. |
| | |
| | 2A) EXIST BLDG CODE 912.2.1 FIRE SPRINKLER SYSTEM. |
| | WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT |
| | REQUIRES AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE |
| | PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH |
| | CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING , SUCH |
| | SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE |
| | CHANGE OF OCCUPANCY OCCURS. |
| | |
| | 2B) 2007 FBC 903.2.1.2 GROUP A-2. AN AUTOMATIC |
| | SPRINKLER SYSTEM SHALL BE PROVIDED FOR GROUP A-2 |
| | OCCUPANCIES WHERE ONE OF THE FOLLOWING CONDITIONS |
| | EXISTS: |
| | |
| | 1. THE FIRE AREA EXCEEDS 5,000 SQUARE FEET (464.5 M2). |
| | |
| | 2. THE FIRE AREA HAS AN OCCUPANT LOAD OF 100 OR MORE. |
| | |
| | 3. THE FIRE AREA IS LOCATED ON A FLOOR OTHER THAN THE |
| | LEVEL OF EXIT DISCHARGE. |
| | |
| | 4. NIGHTCLUBS OR SIMILAR USAGE WHEN OCCUPANT LOAD IS |
| | 100 OR MORE. |
| | |
| | |
| | 3) EXIST BLDG CODE 912.2.2 FIRE ALARM AND DETECTION |
| | SYSTEM. WHERE A CHANGE IN OCCUPANCY CLASSIFICATION |
| | OCCURS THAT REQUIRES A FIRE ALARM AND DETECTION SYSTEM |
| | TO BE PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE |
| | WITH CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING , |
| | SUCH SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE |
| | THE CHANGE OF OCCUPANCY OCCURS. EXISTING ALARM |
| | NOTIFICATION APPLIANCES SHALL BE AUTOMATICALLY |
| | ACTIVATED THROUGHOUT THE BUILDING. WHERE THE BUILDING |
| | IS NOT EQUIPPED WITH A FIRE ALARM SYSTEM, ALARM |
| | NOTIFICATION APPLIANCES SHALL BE PROVIDED THROUGHOUT |
| | THE AREA WHERE THE CHANGE OF OCCUPANCY OCCURS AND SHALL |
| | BE AUTOMATICALLY ACTIVATED. |
| | |
| | 4) 2997 FBC 907.2.1 GROUP A. A MANUAL FIRE ALARM SYSTEM |
| | SHALL BE INSTALLED IN GROUP A OCCUPANCIES HAVING AN |
| | OCCUPANT LOAD OF 300 OR MORE. |
| | PLANS INDICATE THE INSURANCE CERTIFICATE LIMITS THE |
| | OCCUPANT LOAD TO 250 BUT THE OCCUPANT LOAD IS BASED ON |
| | THE WORST CASE SCENARIO OF THE 508 AS INDICATED ON |
| | PLANS WWITHOUT DECLARING AN OCCUPANCY IN THE VACANT |
| | SPACES AS SHOWN ON PLANS. |
| | |
| | 1004.1.1 AREAS WITHOUT FIXED SEATING. THE NUMBER OF |
| | OCCUPANTS SHALL BE COMPUTED AT THE RATE OF ONE OCCUPANT |
| | PER UNIT OF AREA AS PRESCRIBED IN TABLE 1004.1.1. FOR |
| | AREAS WITHOUT FIXED SEATING, THE OCCUPANT LOAD SHALL |
| | NOT BE LESS THAN THAT NUMBER DETERMINED BY DIVIDING THE |
| | FLOOR AREA UNDER CONSIDERATION BY THE OCCUPANT PER UNIT |
| | OF AREA FACTOR ASSIGNED TO THE OCCUPANCY AS SET FORTH |
| | IN TABLE 1004.1.1. WHERE AN INTENDED USE IS NOT LISTED |
| | IN TABLE 1004.1.1, THE BUILDING OFFICIAL SHALL |
| | ESTABLISH A USE BASED ON A LISTED USE THAT MOST NEARLY |
| | RESEMBLES THE INTENDED USE. |
| | |
| | 5) EXISTING BLDG CODE 912.4.2 MEANS OF EGRESS FOR |
| | CHANGE OF USE TO EQUAL OR LOWER HAZARD CATEGORY. WHEN A |
| | CHANGE OF OCCUPANCY CLASSIFICATION IS MADE TO AN EQUAL |
| | OR LESSER HAZARD CATEGORY (HIGHER NUMBER) AS SHOWN IN |
| | TABLE 912.4, EXISTING ELEMENTS OF THE MEANS OF EGRESS |
| | SHALL COMPLY WITH THE REQUIREMENTS OF SECTION 805 FOR |
| | THE NEW OCCUPANCY CLASSIFICATION. NEWLY CONSTRUCTED OR |
| | CONFIGURED MEANS OF EGRESS SHALL COMPLY WITH THE |
| | REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING |
| | CODE, BUILDING . |
| | |
| | 5A ) PLEASE INDICATE HOW 254 OCCUPANTS WILL BE ABLE TO |
| | EXIT THROUGH A 3'-0" DOOR RATED FOR 170 OCCUPANTS (MAIN |
| | ENTRY) . 025.2 ASSEMBLY MAIN EXIT. EVERY ASSEMBLY |
| | OCCUPANCY SHALL BE PROVIDED WITH A MAIN ENTRANCE/EXIT. |
| | THE MINIMUM AGGREGATE WIDTH OF THE MAIN ENTRANCE FOR |
| | GROUP A OCCUPANCIES SHALL BE SUFFICIENT TO ACCOMMODATE |
| | 50 PERCENT OF THE OCCUPANT LOAD AND SHALL BE AT THE |
| | LEVEL OF EXIT DISCHARGE OR SHALL CONNECT TO A STAIRWAY |
| | OR RAMP LEADING TO A STREET. |
| | |
| | 5B) PLEASE INDICATE COMPLIANCE WITH EGRESS PATERNS |
| | PROVIDE EGRESS SIGNAGE AND DIRECTIONALS AS PER TABLE |
| | 1006, 1006.2 FOR STANDBY POWER. |
| | |
| | 5C) DOOR SWING AT THE GAME ROOM TO VACANT SPACE AT |
| | LEFT. 1008.1.2 DOORS SHALL SWING IN THE DIRECTION OF |
| | EGRESS TRAVEL WHERE SERVING AN OCCUPANT LOAD OF 50 OR |
| | MORE PERSONS OR A GROUP H OCCUPANCY. |
| | |
| | 5D) PLANS INDICATE MANY VACANT ROOMS PLEASE REVIEW |
| | SECTION 1014.2 THIS LEAVES ROOMS WITH ONLY ONE MEANS OF |
| | EGRESS WHEN 2 WOULD BE REQUIRED FOR OCCUPANT LOADS 50 |
| | OR GREATER. 1014.2 EGRESS THROUGH INTERVENING SPACES. |
| | EGRESS THROUGH INTERVENING SPACES SHALL COMPLY WITH |
| | THIS SECTION. |
| | |
| | 1.EGRESS FROM A ROOM OR SPACE SHALL NOT PASS THROUGH |
| | ADJOINING OR INTERVENING ROOMS OR AREAS, EXCEPT WHERE |
| | SUCH ADJOINING ROOMS OR AREAS ARE ACCESSORY TO THE AREA |
| | SERVED, ARE NOT A HIGH-HAZARD OCCUPANCY AND PROVIDE A |
| | DISCERNIBLE PATH OF EGRESS TRAVEL TO AN EXIT. |
| | |
| | 6) EXISTING BLDG CODE 912.3 INTERIOR FINISH. IN AREAS |
| | OF THE BUILDING UNDERGOING THE CHANGE OF OCCUPANCY |
| | CLASSIFICATION, THE INTERIOR FINISH OF WALLS AND |
| | CEILINGS SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING , FOR THE NEW OCCUPANCY |
| | CLASSIFICATION. |
| | |
| | 7) 912.8 ACCESSIBILITY. EXISTING BUILDINGS OR PORTIONS |
| | THEREOF THAT UNDERGO A CHANGE OF GROUP OR OCCUPANCY |
| | CLASSIFICATION SHALL COMPLY WITH CHAPTER 11 OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES |
| | DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER |
| | NOTICE. |
| | |
| | OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM |
| | - 5:00 PM. |
| | |
| | JIM WITMER C. B. O. |
| | COMMERCIAL COMBINATION PLAN REVIEW |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | SURVEY: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |