Plan Review Notes
Plan Review Notes For Permit 09070635
Permit Number 09070635
Review Stop P
Sequence Number 1
Notes
Date Text
2009-10-14 17:03:27DENIED
 REFERENCE:
 FBC-2007 EXISTING BUILDING
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 1
 FBC-2007 CHAPTER 11
  
 1. SHT A-3 PER TABLE 1004.1.1 (BLDG) 1,091 SF
 UNCONCENTRATED EQUALS 73 OCCUPANTS, 15 SF CONCENTRATED
 EQUALS 44 OCCUPANTS & 2541 SF STANDING EQUALS 509
 OCCUPANTS FOR A TOTAL OF 636 OCCUPANTS. 636 DIVIDED BY
 2 EQUALS 313 DIVIDED BY 40 EQUALS 8 MALE & 8 FEMALE
 WATER CLOSETS REQUIRED, 9 TOTAL LAVS REQUIRED, 1
 DRINKING FOUNTAIN, & 1 SERVICE SINK, (PER TABLE 403.1
 PLMG). SEE SECTION 910.1 EXISTING BUILDING CODE. -- THE
 OCCUPANCY LOAD IS NOT TO BE DETERMINED BY INSURANCE
 LIMITATIONS.
  
 2, PER SECTION 906.1 ACCESSIBILITY IN PORTIONS OF
 BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH CHAPTER 11 OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3. PER SECTION 106.3.5.1.3 A WATER ISOMETRIC RISER
 DIAGRAM & A SANITARY ISOMETRIC RISER DIAGRAM ARE
 REQUIRED. FOR THE WATER RISER DIAGRAM SHOW ALL PIPE
 SIZES, VALVES AND (WHERE REQUIRED), WATER HAMMER
 ARRESTORS. FOR THE SANITARY RISER DIAGRAM SHOW ALL PIPE
 SIZES, TRAPS, VENTS ETC. SECTIONS 601, 701, 901 & 1001.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  