2009-10-17 13:50:51REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 NO INFORMATION REGARDING THE EXISTING VENTILATION
 SYSTEM OR VENTILATION RATES WAS PROVIDED. WHERE THE
 OCCUPANCY OF AN EXISTING BUILDING OR PART OF AN
 EXISTING BUILDING IS CHANGED SUCH THAT THE NEW
 OCCUPANCY IS SUBJECT TO DIFFERENT KITCHEN EXHAUST
 REQUIREMENTS OR TO INCREASED MECHANICAL VENTILATION
 REQUIREMENTS IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, MECHANICAL , THE INTENT OF THE RESPECTIVE FLORIDA
 BUILDING CODE, MECHANICAL PROVISIONS SHALL BE COMPLIED
 WITH FOR THE NEW OCCUPANCY PER FBC-EB 909.1. PROVIDE
 VANTILATION CALCULATIONS BASED ON FBC-M TABLE 403.3 FOR
 THE NEW OCCUPANCY, BASED ON THE OCCUPANCY
 CLASSIFICATIONS FOUND IN TE TABLE AND SHOW HOW THE
 REQUIRED RATES OF VENTILATION ARE TO BE PROVIDED IN
 ACCORDANCE WITH FBC-M SECTION 403.
  
 NOTE: ANY FUTURE COMMERCIAL KITCHEN VENTILATION SYSTEM
 MAY BE APPLIED FOR UNDER SEPARATE PERMIT AT A LATER
 DATE (PRIOR TO INSTALLATION).
  