Plan Review Notes
Plan Review Notes For Permit 09070635
Permit Number 09070635
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-10-21 08:31:591600 NORTH DIXIE HIGHWAY
  
 1. THE BUILDING WILL BE REQUIRED TO BE COMPLETELY FIRE
 SPRINKLER PROTECTED. THE PLANS SUGGESTS THAT DIFFERENT
 OCCUPANT LOADS EXIST. ONE OCCUPANT LOAD IS STATED ON
 THE PLANS AND ANOTHER ONE REFERS TO INSURANCE
 REGULATIONS. IN EITHER CASE THESE NUMBERS HAVE NO
 BEARING OF THE AVAILABLE SPACE AND THE CAPACITY. THE
 OCCUPANT LOAD SHOWN ON THE PLANS IS INCORRECT.
  
 2. CROWD MANAGERS ARE REQUIRED IN ASSEMBLY OCCUPANCIES
 WITH OCCUPANT LOADS OF 250 OR MORE PERSONS. PLEASE GO
 MARYLAND STATE FIRE MARSHALS OFFICE AND CLICK THE
 ON-LINE CROWD MANAGEMENT TRAINING ICON, WATCH THE
 VIDEO, COMPLETE THE TEST, AND SUBMIT THE CERTIFICATE TO
 THIS OFFICE. THIS IS A MINIMUM CODE REQUIREMENT OF THE
 FLORID FIRE PREVENTION CODE. THE ON-LINE COURSE IS FREE
 AND ONLY TAKES A FEW MINUTES.
  
 3. ALL EXIT DOORS SUBJECT TO AN OCCUPANT LOAD OF 100 OR
 MORE PERSONS SHALL BE EQUIPPED WITH PANIC HARDWARE. NO
 OTHER LOCKS OR LATCHES ARE PERMITTED. THE PLANS SEEM TO
 SUGGEST ON DOOR WITH PANIC HARDWARE.
  
 4. PLANS DO NOT ILLUSTRATE ANY MECHANICAL, ELECTRICAL,
 PLUMBING, FIRE SPRINKLER OR FIRE ALARM SYSTEM DRAWINGS.
 NO ILLUMINATED EXIT SIGNS OR EMERGENCY LIGHT FIXTURES
 ARE ILLUSTRATED ON THE DRAWINGS.
  
 5. PLANS DO NOT INDICATE INTERIOR FINISH
 CLASSIFICATIONS FOR WALLS AND CEILINGS WITHIN THE
 ASSEMBLY OCCUPANCY. MINIMUM FLAME SPREAD REQUIREMENTS
 FOR WALLS AND CEILINGS MATERIALS ARE REQUIRED AND SHALL
 BE DOCUMENTED ON THE PLANS.
  
 6. AT LEAST TWO EXIT DOORS ARE DISPLAYED THAT ARE
 ACCESSED FROM VACANT SPACE WITH DOORS. HOW IS EXIT
 ACCESS MAINTAINED AND CONTROLLED IN THESE AREAS.
  
 7. THE FLOOR PLAN IS VERY CONFUSING AS TO WHAT EXIT
 STRATEGY WILL BE EMPLOYED AT THE FACILITY. NUMEROUS
 WALLS AND HALLWAYS EXIST WHERE EXITING DOES NOT APPEAR
 TO BE CLEAR. A MINIMUM NUMBER OF OCCUPANTS ARE EXPECTED
 TO EXIT THROUGH THE MAIN EXIT DOORS. THE 50 PERCENT
 DISCHARGE CODE OF THE TOTAL OCCUPANT LOAD CANNOT BE
 ACHIEVED AS SHOWN.
  
 8. PLEASE INDICATE SEATING ACCOMMODATIONS FOR THE
 HANDICAPPED.
  
 9. SEPARATE PLANS AND PERMITS REQUIRED FOR THE FIRE
 SPRINKLER AND FIRE ALARM SYSTEMS.
  
 10. THE FIRE SPRINKLER SYSTEM AND FIRE ALARM SYSTEM
 SHALL BE MONITORED BY A UL LISTED CENTRAL STATION
 APPROVED FOR CENTRAL STATION SERVICE.
  
 11. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY HOOD,
 DUCT, AND FIRE SUPPRESSION SYSTEMS FOR THE KITCHEN
 AREA.
  
 12. PLEASE INDICATE TYPE OF CONSTRUCTION OF PLATFORM.
 IS THE PLATFORM PERMANENT OR TEMPORARY.
  
 13. PLEASE INDICATE THE LOCATIONS OF ANY RAMPS OR
 STAIRS FROM PLATFORM.
  
 14. TACTILE SIGN REQUIRED AT EXIT DOORS.
  
 DENIED.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 WEST PALM BEACH FIRE RESCUE
 BUREAU OF FIRE PREVENTION
 500 NORTH DIXIE HIGHWAY
 WEST PALM BEACH, FLORIDA 33401
 (561) 804-4709 PHONE
 (561) 804-4774 FAX
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved