| 2009-10-11 11:32:58 | |
| | ** DENIED ** |
| | |
| | **** THE ELECTRICAL PERMIT AS APPLIED UNDER 09090346 IS |
| | BEING PLACED ON HOLD. NO CODE COMPLIANCE SHOWN FOR |
| | CHANGE IN OCCUPANCY. |
| | |
| | 1) NOTE: THIS IS A CHANGE IN OCCUPANCY WHICH MUST BE |
| | APPLIED FOR UNDER PERMIT BY LICENSED CONTRACTOR. |
| | APPROPRIATE VALUE FOR SCOPE OF WORK NEEDS TO BE ON |
| | APPLICATION FOR VERIFICATION PER FBC 108.3. |
| | |
| | 2) NOTE: A BATHROOM IS SHOWN IN THE ELECTRICAL ROOM. |
| | THIS IS NOT A LOCATION WHICH IS PERMITTED TO BE |
| | ACCESSED BY UNQUALIFIED PERSONS. BOTH DOORS SHOWN |
| | APPEAR THEY WOULD ACTUALLY HIT EACH OTHER? |
| | |
| | 3) NOTE: PLEASE SEE FBC EXISTING BUILDING CODE 2007 |
| | EDITION WITH 2009 SUPPLEMENTS CHAPTER 9, 908 FOR |
| | CHANGES IN OCCUPANCY. THIS REQUIRES THE ELECTRICAL TO |
| | MEET CHAPTER 27 OF THE FBC. PLANS NEED TO BE SUBMITTED |
| | SHOWING ELECTRICAL, ELECTRICAL SERVICE, SERVICE |
| | LOCATIONS, PANEL LOCATIONS, WIRING, BRANCH CIRCUITS, |
| | LOADS, CIRCUITING ETC MEETING CURRENT CODE. |
| | PLEASE SEE 110.26, 110.9, 210, 215.5, 215.3,240, 220, |
| | 230,240, 310, 408.4 ETC. SOME CODE SECTIONS ARE GIVEN |
| | IN GENERAL AS NO ELECTRICAL PLANS WERE SUBMITTED. THE |
| | ELECTRICAL ROOM/LOCATION SHOWN IS OF CONCERN. |
| | PLEASE SEE 700.12F FOR WIRING OF EMERGENCY AND EXIT |
| | LIGHTS SEE COMMENTS BELOW ABOUT EGRESS LIGHTING. |
| | |
| | 4) NOTE: PLEASE SEE FBC 13-101.3.2, FOR CHANGES IN |
| | OCCUPANCY UNDER ENERGY CODE EFFICIENCY REQUIREMENTS. |
| | PLEASE SUBMIT ACCORDINGLY. |
| | |
| | 5) NOTE: PLEASE SHOW MINIMUM EGRESS LIGHTING |
| | REQUIREMENTS PER NFPA-101 7.8, 7.9. PLEASE BE SURE TO |
| | SEE NOTES ABOVE WITH RESPECT TO WIRING OF EMERGENCY AND |
| | EXIT LIGHT FIXTURES PER 700.12F OF THE NEC. |
| | PLANS CONTAIN A NOTE THAT LIGHTING SHALL BE PROVIDED |
| | HOWEVER NO ELECTRICAL PLANS AND DETAILS WERE SUBMITTED. |
| | |
| | 6) NOTE: WHEN SUBMITTING RELEVANT PLANS SHOWING THE |
| | ABOVE MINIMUM REQUIREMENTS MEETING CODE PLEASE BE SURE |
| | THE FOLLOWING CODES ARE LISTED ON PLANS FOR THIS |
| | REVIEW. |
| | 2005 NFPA-70 ( NEC) |
| | 2006 NFPA-101 |
| | 2002 NFPA-72 ( IF APPLICABLE, SEE COMMENTS FROM FIRE |
| | REVIEW AND BUILDING REVIEW IF A SYSTEM IS REQUIRED. |
| | |
| | |
| | 7) NOTE: WHEN RESUBMITTING DOCUMENTS, PLEASE BE SURE TO |
| | SUBMIT TWO COPIES OF ALL PLANS AND DOCUMENTS. FBC 106.1 |
| | ONLY ONE SET SUBMITTED. |
| | |
| | ** IT IS IMPORTANT TO KNOW THAT AS NO MINIMUM PLANS |
| | WERE SUBMITTED FOR REVIEW THE FOLLOWING REVIEW MAY |
| | CREATE NEW COMMENTS WHICH CAN NOT BE MADE AT THIS TIME. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |