Plan Review Notes
Plan Review Notes For Permit 09070635
Permit Number 09070635
Review Stop E
Sequence Number 1
Notes
Date Text
2009-10-11 11:32:58 
 ** DENIED **
  
 **** THE ELECTRICAL PERMIT AS APPLIED UNDER 09090346 IS
 BEING PLACED ON HOLD. NO CODE COMPLIANCE SHOWN FOR
 CHANGE IN OCCUPANCY.
  
 1) NOTE: THIS IS A CHANGE IN OCCUPANCY WHICH MUST BE
 APPLIED FOR UNDER PERMIT BY LICENSED CONTRACTOR.
 APPROPRIATE VALUE FOR SCOPE OF WORK NEEDS TO BE ON
 APPLICATION FOR VERIFICATION PER FBC 108.3.
  
 2) NOTE: A BATHROOM IS SHOWN IN THE ELECTRICAL ROOM.
 THIS IS NOT A LOCATION WHICH IS PERMITTED TO BE
 ACCESSED BY UNQUALIFIED PERSONS. BOTH DOORS SHOWN
 APPEAR THEY WOULD ACTUALLY HIT EACH OTHER?
  
 3) NOTE: PLEASE SEE FBC EXISTING BUILDING CODE 2007
 EDITION WITH 2009 SUPPLEMENTS CHAPTER 9, 908 FOR
 CHANGES IN OCCUPANCY. THIS REQUIRES THE ELECTRICAL TO
 MEET CHAPTER 27 OF THE FBC. PLANS NEED TO BE SUBMITTED
 SHOWING ELECTRICAL, ELECTRICAL SERVICE, SERVICE
 LOCATIONS, PANEL LOCATIONS, WIRING, BRANCH CIRCUITS,
 LOADS, CIRCUITING ETC MEETING CURRENT CODE.
 PLEASE SEE 110.26, 110.9, 210, 215.5, 215.3,240, 220,
 230,240, 310, 408.4 ETC. SOME CODE SECTIONS ARE GIVEN
 IN GENERAL AS NO ELECTRICAL PLANS WERE SUBMITTED. THE
 ELECTRICAL ROOM/LOCATION SHOWN IS OF CONCERN.
 PLEASE SEE 700.12F FOR WIRING OF EMERGENCY AND EXIT
 LIGHTS SEE COMMENTS BELOW ABOUT EGRESS LIGHTING.
  
 4) NOTE: PLEASE SEE FBC 13-101.3.2, FOR CHANGES IN
 OCCUPANCY UNDER ENERGY CODE EFFICIENCY REQUIREMENTS.
 PLEASE SUBMIT ACCORDINGLY.
  
 5) NOTE: PLEASE SHOW MINIMUM EGRESS LIGHTING
 REQUIREMENTS PER NFPA-101 7.8, 7.9. PLEASE BE SURE TO
 SEE NOTES ABOVE WITH RESPECT TO WIRING OF EMERGENCY AND
 EXIT LIGHT FIXTURES PER 700.12F OF THE NEC.
 PLANS CONTAIN A NOTE THAT LIGHTING SHALL BE PROVIDED
 HOWEVER NO ELECTRICAL PLANS AND DETAILS WERE SUBMITTED.
  
 6) NOTE: WHEN SUBMITTING RELEVANT PLANS SHOWING THE
 ABOVE MINIMUM REQUIREMENTS MEETING CODE PLEASE BE SURE
 THE FOLLOWING CODES ARE LISTED ON PLANS FOR THIS
 REVIEW.
 2005 NFPA-70 ( NEC)
 2006 NFPA-101
 2002 NFPA-72 ( IF APPLICABLE, SEE COMMENTS FROM FIRE
 REVIEW AND BUILDING REVIEW IF A SYSTEM IS REQUIRED.
  
  
 7) NOTE: WHEN RESUBMITTING DOCUMENTS, PLEASE BE SURE TO
 SUBMIT TWO COPIES OF ALL PLANS AND DOCUMENTS. FBC 106.1
 ONLY ONE SET SUBMITTED.
  
 ** IT IS IMPORTANT TO KNOW THAT AS NO MINIMUM PLANS
 WERE SUBMITTED FOR REVIEW THE FOLLOWING REVIEW MAY
 CREATE NEW COMMENTS WHICH CAN NOT BE MADE AT THIS TIME.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  