Plan Review Notes
Plan Review Notes For Permit 09070624
Permit Number 09070624
Review Stop E
Sequence Number 3
Notes
Date Text
2009-09-15 17:57:44 
 ** PROVISO **
  
  
 1) NOTE: FINAL APPROVAL OF INTERCONNECTION DOCUMENTS
 FROM FLORIDA POWER AND LIGHT TO BE SUBMITTED FOR FILE.
  
 2) NOTE: REDLINED PLANS: THE OPTIONAL METER SHOWN ON
 RISER WHICH IS NOTED TO BE INSTALLED BY OTHERS SHALL BE
 UNDER SEPARATE PERMIT IF NOT INSTALLED BY FPL.
 RISER SHALL BE REVISED BEFORE FINAL IN ORDER TO REFLECT
 ACCURATELY WHAT WAS INSTALLED EVEN IF INSTALLED BY
 OTHERS.
 ONLY WORK DONE AND INSTALLED BY THE UTILITY COMPANY IS
 EXEMPT FROM PERMITTING. ALL OTHER WORK SHALL OBTAIN
 PERMIT.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  