2009-09-08 11:01:10** DENIED REVIEW **
  
 ** COMMENTS #1 AND #2 FROM PREVIOUS REVIEW ARE STILL IN
 NEED OF ADDRESSING.
  
 1) NOTE: NO PRODUCT CUT SHEETS/SPECS SUBMITTED. 110.3
  
 2) NOTE: NO LETTER SUBMITTED FROM FPL THAT INSTALLATION
 WILL MEET THEIR SERVICE STANDARDS. PLANS NOW STATE THAT
 A UTILITY BI-DIRECTIONAL METER WILL BE INSTALLED BY
 OTHERS.
 THE APPLIED SCOPE OF WORK IS NOT PERMITTED UNTIL
 SERVICE WORK IS CLEARED UP.
 THIS IS A 1000AMP SERVICE.
  
 3) NOTE: SHOW LOCATIONS OF DISCONNECTING MEANS MEETING
 690.13,14,15, 230.2E
  