| Plan Review Notes For Permit 09070624 |
| Permit Number |
09070624 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2009-09-08 11:01:10 | ** DENIED REVIEW ** | | | | | | ** COMMENTS #1 AND #2 FROM PREVIOUS REVIEW ARE STILL IN | | | NEED OF ADDRESSING. | | | | | | 1) NOTE: NO PRODUCT CUT SHEETS/SPECS SUBMITTED. 110.3 | | | | | | 2) NOTE: NO LETTER SUBMITTED FROM FPL THAT INSTALLATION | | | WILL MEET THEIR SERVICE STANDARDS. PLANS NOW STATE THAT | | | A UTILITY BI-DIRECTIONAL METER WILL BE INSTALLED BY | | | OTHERS. | | | THE APPLIED SCOPE OF WORK IS NOT PERMITTED UNTIL | | | SERVICE WORK IS CLEARED UP. | | | THIS IS A 1000AMP SERVICE. | | | | | | 3) NOTE: SHOW LOCATIONS OF DISCONNECTING MEANS MEETING | | | 690.13,14,15, 230.2E | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|