| Plan Review Notes For Permit 09070624 |
| Permit Number |
09070624 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-08-12 10:55:05 | | | | ** DENIED REVIEW ** | | | | | | 1) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT | | | SHEETS FOR THE PROPOSED PHOTOVOLTAIC SYSTEM. PLEASE BE | | | SURE LISTING FROM A NATIONALLY RECOGNIZED TESTING | | | LABORATORY IS SHOWN. ( NRTL) 110.3 | | | | | | 2) NOTE: PLEASE SEE PHOTOVOLTAIC RISER WHICH INDICATES | | | THE SERVICE AS HAVING A *MULTI-DIRECTIONAL METER*. | | | BASED ON THE ORIGINAL RISER AND PLANS THIS IS A 1000AMP | | | SERVICE. HOW DOES THIS SIZE SERVICE HAVE A | | | MULTI-DIRECTIONAL METER? | | | PLEASE OBTAIN LETTER FROM LOCAL POWER COMPANY FLORIDA | | | POWER AND LIGHT ( FPL) FOR THE INSTALLATION MEETING | | | SERVICE STANDARDS. | | | | | | 3) NOTE: PLEASE SEE NOTES ON PLANS MENTIONS COLOR | | | CODING FROM THE 1990 NATIONAL ELECTRICAL CODE. ( | | | SPECIFICALLY) PLEASE BE SURE TO REVISE. | | | THE PLANS ARE UNDER THE 2005 NEC. | | | | | | 4) NOTE: PLEASE INDICATE PROTECTION PER 690.6 (D). | | | | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|