2009-08-12 10:55:05 
 ** DENIED REVIEW **
  
 1) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE PROPOSED PHOTOVOLTAIC SYSTEM. PLEASE BE
 SURE LISTING FROM A NATIONALLY RECOGNIZED TESTING
 LABORATORY IS SHOWN. ( NRTL) 110.3
  
 2) NOTE: PLEASE SEE PHOTOVOLTAIC RISER WHICH INDICATES
 THE SERVICE AS HAVING A *MULTI-DIRECTIONAL METER*.
 BASED ON THE ORIGINAL RISER AND PLANS THIS IS A 1000AMP
 SERVICE. HOW DOES THIS SIZE SERVICE HAVE A
 MULTI-DIRECTIONAL METER?
 PLEASE OBTAIN LETTER FROM LOCAL POWER COMPANY FLORIDA
 POWER AND LIGHT ( FPL) FOR THE INSTALLATION MEETING
 SERVICE STANDARDS.
  
 3) NOTE: PLEASE SEE NOTES ON PLANS MENTIONS COLOR
 CODING FROM THE 1990 NATIONAL ELECTRICAL CODE. (
 SPECIFICALLY) PLEASE BE SURE TO REVISE.
 THE PLANS ARE UNDER THE 2005 NEC.
  
 4) NOTE: PLEASE INDICATE PROTECTION PER 690.6 (D).
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  