2009-08-12 08:31:25BUILDING PLAN REVIEW
 PERMIT: 09070601
 ADD: 110 RUSSLYN DR
 CONT: O/ B FORREST, CAROLINE, K
 TEL: (561)951-4122
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 SUPPLEMENTS.
  
 PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING
 BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO
 WHAT LEVEL ALTERATION WILL BE COMPLETED UNDERTHIS
 PERMIT.
 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE.
  
 2) (2004 FBC) 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE &
 EXTENT OF THE WORK PROPOSED & SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, AND RULES AND REGULATIONS AS
 DETERMINED BY THE BUILDING OFFICIAL. THE PERMIT
 APPLICATION UNDER DESCRIPTION OF WORK DOES NOT REFLECT
 THE AMOUNT OF WORK SHOWN ON THE PLANS. PLEASE
 COORDINATE!
  
 3) SHEET S100 DOES NOT INDICATE THE EXISTING NOR THE
 NEW FINISH FLOOR ELEVATIONS. PLEASE NOTE THIS PROPERTY
 IS LOCATED IN A FLOOD ZONE A5 WITH THE BASE FLOOD
 ELEVATION OF 7'-0" PLUS THE CITY REQUIREMENT OF AN
 ADDITIONAL 6 INCHES OR FINISH FLOOR OF 7'-6" . THIS
 REQUIREMENT WOULD BE FOR ANY A/C EQUIPMENT PADS. PLEASE
 NOTE TTHE FINISH FLOOR ELEVATIONS ON THE PLANS.
 PLEASE SEE ATTACHED DOCUMENTS.
  
 4) SHEET S100:
 4A) INDICATES THE USE OF GROUTED CELLS AND THE USE OF A
 CONCRETE BEAM, THE PLANS DO NOT PROVIDE THE STRENGTH OF
 THE GROUTE NOR THE STRENGTH NOR TYPE OF CONCRETE TO BE
 USED IN THE CONCRETE BEAM.
 901.2 PLAIN AND REINFORCED CONCRETE. STRUCTURAL
 CONCRETE SHALL BE DESIGNED AND CONSTRUCTED IN
 ACCORDANCE WITH THE REQUIREMENTS OF THIS CHAPTER AND
 ACI 318 AS AMENDED IN SECTION 1908 OF THIS CODE. EXCEPT
 FOR THE PROVISIONS OF SECTIONS 1904 AND 1910, THE
 DESIGN AND CONSTRUCTION OF SLABS ON GRADE SHALL NOT BE
 GOVERNED BY THIS CHAPTER UNLESS THEY TRANSMIT VERTICAL
 LOADS OR LATERAL FORCES FROM OTHER PARTS OF THE
 STRUCTURE TO THE SOIL.
 1901.4 CONSTRUCTION DOCUMENTS. THE CONSTRUCTION
 DOCUMENTS FOR STRUCTURAL CONCRETE CONSTRUCTION SHALL
 INCLUDE:
  
 1. THE SPECIFIED COMPRESSIVE STRENGTH OF CONCRETE AT
 THE STATED AGES OR STAGES OF CONSTRUCTION FOR WHICH
 EACH CONCRETE ELEMENT IS DESIGNED.
  
 2. THE SPECIFIED STRENGTH OR GRADE OF REINFORCEMENT.
  
 3. THE SIZE AND LOCATION OF STRUCTURAL ELEMENTS,
 REINFORCEMENT, AND ANCHORS.
  
 PLEASE NOTE THAT GROUT AND PUMP MIX ARE NOT THE SAME
 MIX!
  
 4B) THE GAGARGE APPEARS TO ALSO HAVE A CONCRETE BEAM
 WITH NO INFORMATION A TO SIZE SHEET A100 APPEARSS TO
 HAVE LIGHTS HANGING FROM THE BEAM ? CUT SECTION AA ONLY
 PROVIDES A DETAIL OF THE FOOTING NOT THE BEAM?
  
 5) SHEET S100 ALSO DOES NOT HAVE ANY INFORMATION ABOUT
 TERMITE PROTECTION FOR THE NEW SLABS.
 1816.1 TERMITE PROTECTION. TERMITE PROTECTION SHALL BE
 PROVIDED BY REGISTERED TERMITICIDES, INCLUDING
 SOIL-APPLIED PESTICIDES, BAITING SYSTEMS AND PESTICIDES
 APPLIED TO WOOD, OR OTHER APPROVED METHODS OF TERMITE
 PROTECTION LABELED FOR USE AS A PREVENTATIVE TREATMENT
 TO NEW CONSTRUCTION. SEE SECTION 202, REGISTERED
 TERMITICIDE. UPON COMPLETION OF THE APPLICATION OF THE
 TERMITE PROTECTIVE TREATMENT, A CERTIFICATE OF
 COMPLIANCE SHALL BE ISSUED TO THE BUILDING DEPARTMENT
 BY THE LICENSED PEST CONTROL COMPANY THAT CONTAINS THE
 FOLLOWING STATEMENT: "THE BUILDING HAS RECEIVED A
 COMPLETE TREATMENT FOR THE PREVENTION OF SUBTERRANEAN
 TERMITES. TREATMENT IS IN ACCORDANCE WITH RULES AND
 LAWS ESTABLISHED BY THE FLORIDA DEPARTMENT OF
 AGRICULTURE AND CONSUMER SERVICES."
  
 6) SHEET S100 NEW SLAB INFORMATION DOES NOT PROVIDE THE
 MINIMUM STRENGTH OF CONCRETE FOR THE SLAB. 106.1.2
 ADDITIONAL INFORMATION.
  
 7) SHEET S100 INDICATES NEW CONCRETE BLOCK GOUTED CELLS
 ON BOTH SIDES OF THE GARAGE DOOR OPENING. PLANS DO NOT
 INDICATE ANY BEAM ABOVE THE GARAGE DOOR OPENING PLEASE
 PROVIDE ADDITIONAL INFORMATION 106.1.2.
  
 8) SHEET S100 ALSO INDICATES THE USE OF (2) 2X10'S @
 4-0" O. C. WITH 3/4 " PLYWOOD. R803.2.2 ALLOWABLE
 SPANS. THE MAXIMUM ALLOWABLE SPANS FOR WOOD STRUCTURAL
 PANEL ROOF SHEATHING SHALL NOT EXCEED THE VALUES SET
 FORTH IN TABLE R503.2.1.1(1), OR APA E30.
  
 8A) THERE ARE TWO ISSUES AT HAND, FIRST THE RAFTERS 2@
 2X10'S PLEASE PROVIDE THE SPECIES AND GRADE OF WOOD TO
 BE USED FOR RAFTERS.
  
 8B) THE ALLOWABLE SPANS FOR WOOD STRUCTURAL PANEL ROOF
 SHEATHING FOUND IN APA E30 INDICATES A FOOTNOTE (B)
 THAT EITHER REQUIRES 2 PANEL CLIPS PER SPAN OR EDGE
 SUPPORTS MAY BE PROVIDED BY TONGUE AND GROOVE EDGES OR
 BY SOLID BLOCKING. PLEASE INDICATE WHICH OF THESE
 OPTIONS YOU PLAN ON USING.
  
 9) SHEET A300 :
  
 9A) PLANS FAIL TO INDICATE THE R-VALUE OF THE
 ROOF-CEILING INSULATION TO BE INSTALLED.
  
 9B) PLANS ALSO FAIL TO INDICATE THE THICKNESS OF THE
 CEILING DRYWALLAND THE ADDITIONAL SUPPORTS REQUIRED TO
 HANG THE CEILING FROM. PLEASE ALSO PROVIDE THE LIVE &
 DEAD LOADS AS WELL AS DEFLECTION LEVELS.
  
 9C) THE ELEVATIONS INDICATE THE REUSING OF THE EXISTING
 SLIDDING GLASS DOORS PROVIDE DOCUMENTATION THAT THEY
 MEET WIND PRESSURES. THE EXISTING DOORS WILL NOT NEED
 TO MEET LARGE MISSILE TESTING IF :
 A)EXISTING BUILDING CODE 606.5 OPENINGS IN SUNROOMS,
 ENCLOSED BALCONIES AND ENCLOSED PORCHES CONSTRUCTED
 UNDER EXISTING ROOFS OR DECKS ARE NOT REQUIRED TO BE
 PROTECTED, PROVIDED THE SPACE IS SEPARATED FROM THE
 BUILDING INTERIOR BY A WALL AND ALL OPENINGS IN THE
 SEPARATING WALL ARE PROTECTED IN ACCORDANCE WITH
 SECTION 1609.1.2 OF THE FLORIDA BUILDING
 CODE, BUILDING . SUCH SPACES SHALL BE PERMITTED TO BE
 DESIGNED AS ENCLOSED OR PARTIALLY ENCLOSED.
 OR
 B) SHUTTERS TO BE APPLIED TO THE NEW LOGGIA SLIDING
 GLASS DOOR OPENINGS. 2007FBC/ 1609.1.2
 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS REGIONS,
 EXTERIOR GLAZING THAT RECEIVES POSITIVE PRESSURE IN THE
 LOWER 60 FEET (18.3 M) IN BUILDINGS SHALL BE ASSUMED TO
 BE OPENINGS AND THE BALANCE OF GLAZED OPENINGS IN THE
 REST OF THE BUILDING SHALL BE ASSUMED TO BE ZERO UNLESS
 SUCH GLAZING THAT RECEIVES POSITIVE PRESSURE IS IMPACT
 RESISTANT OR PROTECTED WITH AN IMPACT RESISTANT
 COVERING MEETING THE REQUIREMENTS OF SSTD 12, ASTM E
 1886 AND ASTM E 1996, OR MIAMI-DADE TAS 201, 202 AND
 203 REFERENCED THEREIN AS FOLLOWS: 1. GLAZED OPENINGS
 LOCATED WITHIN 30 FEET (9.1 M) OF GRADE SHALL MEET THE
 REQUIREMENTS OF THE LARGE MISSILE TEST. 2. GLAZED
 OPENINGS LOCATED MORE THAN 30 FEET (9.1 M) ABOVE GRADE
 SHALL MEET THE PROVISIONS OF THE SMALL MISSILE TEST.
  
 9D) THE PLANS APPEAR TO HAVE THE ROOF FRAMING MEMBERS
 TO CONTINUE OVER THE EXISTING FOYER AREA, PLEASE
 PROVIDE FRAMING DETAILS AS TO THE SIZE & FREQUENCY OF
 FRAMING MEMBERS, SPECIES OF WOOD AND GRADE . PLEASE
 ALSO PROVIDE TIE DOWN INFORMATION FOR THESE FRAMING
 MEMBERS.
  
 10) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 10A) SLIDING GLASSS DOORS IF 9A IS NOT APPLIED. 9B-72
 B) TRUSS ANCHORS 9B-72
  
 11) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL. ROOFING APPROVAL
 DOES NOT HAVE SHOP DRAWING STAMP.
  
 12) ROOFING ASSEMBLIES APPROVAL NOA 07-0730.03 PAGE 16
 IS INDICATED AS THE SUB-SYSTEM TO BE INSTALLED. THE
 INDICATED DESIGN PRESSURE OF -52.5 IS INDICATED AND
 LIMITATION# 7 APPLIES REQUIRING ENHANCED FASTENING IN
 ZONES 2& 3 RAS 117 APPLIES, PROVIDE FASTENING FOR ZONES
 2&3.
  
 13) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 ELECTRICAL COMMENTS:
 2005 NEC
 1) GARAGE OUTLETS NEED TO INDICATE THEY ARE
 GROUND-FAULT CIRCUIT- INTERRUPTER CIRCUIT PER
 210.8(A)(2) GARAGES.
  
 2) LOGGIA: WALL OUTLETS ARE MISSING PER SECTION
 210.52(A)(1)-(A)(3).
  
 3) PLEASE INDICATE COMPLIANCE WITH EITHER EXISTING OR
 NEW OUTLETS PER 210.52(5)(E) OUTDOOR OUTLETS.
  
 4) LOGGIA ROOM ITSELF DOES NOT HAVE LIGHTING OUTLETS
 WITHIN THE ROOM PER 210.70(A)(1) HABITABLE ROOMS
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
 SFP-100
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved