| 2009-07-29 08:26:57 | REVISION REQUIRED | | | PROVIDE INSTALLATION SCHEDULE | | | | | | NOTE THAT "FLOOR MOUNT" IS HIGHLIGHTED. SEE SHEET 11 OF | | | THE PRODUCT APPROVAL. MINIMUM CONCRETE STRENGTH | | | REQUIRED IS 3000PSI; CONCRETE SLAB IS USUALLY 2500PSI. | | | EITHER PROVIDE EVIDENCE THAT THE CONCRETE MEETS MINIMUM | | | STRENGTH OR REVISE ANCHOR SPACING. | | | |
|