2009-08-04 13:38:00REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. A MECHANICAL PERMIT HAS BEEN APPLIED FOR, YET NO
 MECHANICAL SCOPE OF WORK IS SHOWN ON PLANS. DUCT
 SYSTEMS SHALL BE DESCRIBED IN SUFFICIENT DETAIL TO
 ALLOW THE BUILDING OFFICIAL TO DETERMINE CODE
 COMPLIANCE IN ACCORDANCE WITH FBC-R SECTION N1110.A.1.
  
 2. EVERY BUILDING FOR WHICH A PERMIT FOR NEW
 CONSTRUCTION IS ISSUED HAVING A FOSSIL-FUEL-BURNING
 HEATER OR APPLIANCE, A FIREPLACE, OR AN ATTACHED GARAGE
 SHALL HAVE AN OPERATIONAL CARBON MONOXIDE ALARM
 INSTALLED WITHIN 10 FEET OF EACH ROOM USED FOR SLEEPING
 PURPOSES IN ACCORDANCE WITH FBC-R313.4.
  
 3. PAGE A2 SHOWS NEW BATH EXHAUST FAN. SHOW LOCATION OF
 EXHAUST DUCT TERMINATION AND DISCHARGE LOCATION IN
 ACCORDANCE WITH FBC-R303.4 AND FBC-R SECTION M1501.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]