| Plan Review Notes For Permit 09070587 |
| Permit Number |
09070587 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-08-04 13:38:00 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. A MECHANICAL PERMIT HAS BEEN APPLIED FOR, YET NO | | | MECHANICAL SCOPE OF WORK IS SHOWN ON PLANS. DUCT | | | SYSTEMS SHALL BE DESCRIBED IN SUFFICIENT DETAIL TO | | | ALLOW THE BUILDING OFFICIAL TO DETERMINE CODE | | | COMPLIANCE IN ACCORDANCE WITH FBC-R SECTION N1110.A.1. | | | | | | 2. EVERY BUILDING FOR WHICH A PERMIT FOR NEW | | | CONSTRUCTION IS ISSUED HAVING A FOSSIL-FUEL-BURNING | | | HEATER OR APPLIANCE, A FIREPLACE, OR AN ATTACHED GARAGE | | | SHALL HAVE AN OPERATIONAL CARBON MONOXIDE ALARM | | | INSTALLED WITHIN 10 FEET OF EACH ROOM USED FOR SLEEPING | | | PURPOSES IN ACCORDANCE WITH FBC-R313.4. | | | | | | 3. PAGE A2 SHOWS NEW BATH EXHAUST FAN. SHOW LOCATION OF | | | EXHAUST DUCT TERMINATION AND DISCHARGE LOCATION IN | | | ACCORDANCE WITH FBC-R303.4 AND FBC-R SECTION M1501.1. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|