| Plan Review Notes For Permit 09070587 |
| Permit Number |
09070587 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-08-13 13:11:45 | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009 | | | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND | | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} 9B-3.0472 CARBON MONOXIDE PROTECTION. | | | (1) EVERY BUILDING FOR WHICH A PERMIT FOR NEW | | | CONSTRUCTION IS ISSUED ON OR AFTER 7/1/08 AND HAVING A | | | FOSSIL-FUEL-BURNING HEATER OR APPLIANCE, A FIREPLACE, | | | OR AN ATTACHED GARAGE SHALL HAVE AN OPERATIONAL CARBON | | | MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH ROOM | | | USED FOR SLEEPING PURPOSES. COMBINATION SMOKE/CARBON | | | MONOXIDE ALARMS SHALL BE LISTED OR LABELED BY A | | | NATIONALLY RECOGNIZED TESTING LABORATORY. | | | | | | 2} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.2 | | | RESIDENTIAL FLORIDA BUILDING CODE. | | | | | | 3} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE | | | PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI | | | PROTECTED PER 210.8(A) (1).***THE ADDED BATH DOES NOT | | | COMPLY WITH SPACING.ALSO THE NEW BATH CIRCUIT INDICATES | | | THE UTILITY ROOM LISTED ON THE PANEL SCHEDULE IN | | | VIOLATION OF 210.11(C)(3). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|