| 2009-08-14 15:30:27 | 2007 FBC W/2009 REVISIONS |
| | ADDITION |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) NOTE: IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) UPDATE REFERENCES TO THE 2007 FBC W/2009 REVISIONS. |
| | SHEETS A1 AND A3 SPECIFY THE 2004 FBC. |
| | |
| | 3) ON SHEET A3 ONE OF THE NOTES FOR THE TYPICAL WALL |
| | SECTION APPEARS TO BE MISSING SOME OF THE TEXT. IT |
| | STATES " 8'- 0" O.C. W/ 8D NAILS. PLEASE CLARIFY. |
| | |
| | 4) SHOW COMPLIANCE WITH FBC R313.4 FOR CARBON MONOXIDE |
| | PROTECTION. |
| | |
| | 5) THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE |
| | ENERGY CALCULATION FORMS. 2007 ENERGY GLITCH AMENDMENTS |
| | N1100.2.2 |
| | |
| | 6) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 7) ON THE DOOR SCHEDULE ON A3 THE OPENING WITH FOR THE |
| | 16' WIDE GARAGE DOOR IS SPECIFIED AS 108" (9') WIDE. |
| | |
| | 8) SUBMIT PRODUCT APPROVALS FOR THE TRUSS CONNECTORS OR |
| | SPECIFY THE NOA OR FL# ON THE PLANS. DCA RULE 9B-72 |
| | |
| | 9) SUBMIT PRODUCT APPROVALS FOR THE 8" PRECAST CONCRETE |
| | LINTELS. DCA RULE 9B-72 |
| | |
| | 10) THE NEW FRONT DOOR SHOWN ON THE PLANS HAS SIDELITES |
| | AND IS GLAZED. THE PRODUCT APPROVAL SUBMITTED FOR THE |
| | DOORS IS FOR UNGLAZED DOORS WITH NON-IMPACT RATED |
| | SIDELITES. SUBMIT PRODUCT APPROVALS FOR IMPACT RATED |
| | FRONT DOOR ASSEMBLY OR PRODUCT APPROVALS FOR THE IMPACT |
| | PROTECTION THAT WILL BE INSTALLED. |
| | |
| | 11) PROVIDE A CONSTRUCTION DETAIL FOR THE ARCH AT THE |
| | NEW ENTRY. FBC R601.2 |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |