2009-07-30 10:59:25 
  
 ** DENIED REVIEW **
  
 ** CODE SECTIONS NOTED ARE FROM THE 2007 FBC WITH THE
 2009 REVISIONS.
  
 1) NOTE: PLEASE PROVIDE LIGHTING PERFORMANCE
 CALCULATIONS PER 13-415.AB.5, 13-415.AB.2.2.
  
 2) NOTE: PLEASE LIST THE TYPE OF TIME CLOCKS PER
 13-415.AB.2.2.
 MUST BE AN ASTRONOMICAL TIME CLOCK WITH A MINIMUM OF
 10HR BACK UP.
 OR PHOTO-SENSOR CONTROLS.
  
 3) NOTE: PLEASE PROVIDE LOADS FOR LIGHTING AND
 CIRCUITING TO PANELS WITH THE SIZE OF THE OVER CURRENT
 PROTECTION DEVICES AND CONDUCTORS SIZES.
 408.4,310.16,240.4
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II