2009-08-10 14:08:01*****DENIED*****
  
  
 1. IN THE GENERAL ELECTRIC NOTES ON SHEET E-1, AMEND
 NOTE #1 TO REFLECT THE 2006 NFPA-101 AND 2005 NFPA-110
 EDITIONS.
  
 2. ON SHEET E-1, NFPA 101.7.10.2 AND 101.7.10.3 ARE
 REFERENCED IN THE NOTES. THIS WRITER COULD NOT LOCATE
 THESE VERBAGE IN EITHER THE 2003 OR 2006 EDITION OF
 NFPA 101.
  
 3. NO FLOOR PLAN AND/OR SITE PLAN TO INDICATE LOCATION
 OF THE EXISTING/PROPOSED GENERATOR.
  
 4. SHOW THE PROXIMITY OF ANY ANY EXIT DOORS, AIR INTAKE
 OR EXHAUST OPENINGS WITHIN TEN FEET OF THE GENERATOR
 AND OR FUEL TANK.
  
 5. NO WARNING LABELS OR PRODUCT LABELS DESCRIBED.
  
 6. WHAT SYSTEMS WILL THE GENERATOR SUPPLY?
  
 7. HOW IS THE FUEL TANK PROPOSED TO BE REFILLED SAFELY.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  