| Plan Review Notes For Permit 09070449 |
| Permit Number |
09070449 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-08-10 14:08:01 | *****DENIED***** | | | | | | | | | 1. IN THE GENERAL ELECTRIC NOTES ON SHEET E-1, AMEND | | | NOTE #1 TO REFLECT THE 2006 NFPA-101 AND 2005 NFPA-110 | | | EDITIONS. | | | | | | 2. ON SHEET E-1, NFPA 101.7.10.2 AND 101.7.10.3 ARE | | | REFERENCED IN THE NOTES. THIS WRITER COULD NOT LOCATE | | | THESE VERBAGE IN EITHER THE 2003 OR 2006 EDITION OF | | | NFPA 101. | | | | | | 3. NO FLOOR PLAN AND/OR SITE PLAN TO INDICATE LOCATION | | | OF THE EXISTING/PROPOSED GENERATOR. | | | | | | 4. SHOW THE PROXIMITY OF ANY ANY EXIT DOORS, AIR INTAKE | | | OR EXHAUST OPENINGS WITHIN TEN FEET OF THE GENERATOR | | | AND OR FUEL TANK. | | | | | | 5. NO WARNING LABELS OR PRODUCT LABELS DESCRIBED. | | | | | | 6. WHAT SYSTEMS WILL THE GENERATOR SUPPLY? | | | | | | 7. HOW IS THE FUEL TANK PROPOSED TO BE REFILLED SAFELY. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|