Plan Review Notes
Plan Review Notes For Permit 09070449
Permit Number 09070449
Review Stop E
Sequence Number 1
Notes
Date Text
2009-08-26 11:01:31 
 ** DENIED REVIEW **
  
 1) NOTE: ALL OF THE FOLLOWING CODES SHALL BE LISTED ON
 PLANS FOR MINIMUM DESIGN.
 2005 NFPA-70
 2006 NFPA-101
 2005 NFPA-110
  
 2) NOTE: ** PLANS ARE NOT COMPLETE WITH ENOUGH
 INFORMATION FOR REVIEW FOR CODE COMPLIANCE. THE PLANS
 STATE THIS IS A LEVEL 2, CLASS X TYPE 60 UNIT, HOWEVER
 BASED ON THE PANEL SCHEDULE THIS IS NOT POSSIBLE.
 PLEASE SUBMIT AND SHOW ALL INFORMATION ON THE TYPE AND
 CLASS OF SYSTEMS. PLEASE LOOK AT 700.9 OF THE NEC FOR
 WIRING OF SYSTEMS. BASE DON THE SCHEDULE THERE ARE WHAT
 APPEARS TO BE 700 SYSTEMS, POSSIBLY 701 SYSTEMS AND
 THERE ARE 702 SYSTEMS ALL SHOWN ON THE SAME TRANSFER
 SWITCH. THIS IS NOT PERMITTED.
 THIS IS NOT A CLASS X TYPE 60 LEVEL 2 SYSTEMS.
 PLEASE SEE NFPA-110 CHAPTER 4, THIS WOULD BE A LEVEL 1,
 TYPE 10, CLASS 2 AT A MINIMUM. DESIGN ACCORDINGLY. SEE
 NEC 700.12 ( ALL) FOR BACK UP OF EMERGENCY LIGHTS WITH
 ACCEPTABLE POWER AND MINIMUM TIME TO COME ON.
 CLASS X PER NFPA-110 IS A HIGHER AMOUNT OF FUEL THAN
 SHOWN.
  
 2) NOTE: PLEASE SEE 700.27, 701.18 OF THE NEC AND
 NFPA-110 6.5 (ALL)
  
 3) NOTE: PLEASE SEE NFPA-110 7.3.1 AND PROVIDE LIGHTING
 ACCORDINGLY
  
 4) NOTE: PLEASE SEE NFPA-110 7.2, 7.2.1, 7.2.1.2, ETC.
 BASED ON THE SUBMITTED PLANS THIS EQUIPMENT/ EPS IS
 PART OF A 700 SYSTEM WHICH IS NOT PERMITTED IN THE
 MECHANICAL EQUIPMENT ROOM.
 PLEASE SHOW LOCATIONS OF ALL ELECTRICAL EQUIPMENT.
  
 5) NOTE: PLEASE PROVIDE INFORMATION ON RISER ON WHETHER
 OR NOT THE ATS WILL BE 4-POLE OR 3-POLE. THE RISER
 INDICATES A NEW GROUND HOWEVER NO INFORMATION ON THE
 ATTACHMENT IS SHOWN.
 SEE NFPA-110 6.2.15
  
 6) NOTE: HOW WILL THE POWER BE SHUT DOWN IN THE EVENT
 OF AN EMERGENCY WHEN FIRE DEPARTMENT OR OTHER PERSONNEL
 SHUTS DOWN MAINS POWER AND THE GENERATOR WHICH IS
 LOCATED ON THE ROOF AREA STARTS AND RE-FEEDS 480V
 ELECTRICAL SYSTEMS?
 SEE 445.18 ETC.
 SEE COMMENTS FROM FIRE MARSHAL.
  
 ** AS THERE WILL BE CHANGES TO THE DESIGN, SOME NEW
 COMMENTS MAY ARISE ONCE MORE INFORMATION IS SUBMITTED
 AND/OR DESIGN CHANGES HAVE BEEN MADE.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  