| 2009-08-04 15:31:51 | **PROVISOS** | | | 1. CONDENSATE DRAIN LINE HORIZONTAL SECTION AS SHOWN IS | | | VERY LONG. CONDENSATE PIPING SHALL BE INSTALLED AT A | | | UNIFORM 1/8 INCH PER FOOT IN ACCORDANCE WITH FBC-M | | | 307.2.2. | | | | | | 2. PROVIDE THE ACTUAL PRODUCT APPROVAL DOCUMENTATION | | | WITH INSTALLATION INSTRUCTIONS ON SITE FOR FIELD | | | INSPECTOR TO VERIFY SIZE OF CONDENSING UNIT IS | | | COMPATIBLE WITH THE PROPOSED STAND. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|