Plan Review Notes
Plan Review Notes For Permit 09070433
Permit Number 09070433
Review Stop M
Sequence Number 1
Notes
Date Text
2009-08-04 15:31:51**PROVISOS**
 1. CONDENSATE DRAIN LINE HORIZONTAL SECTION AS SHOWN IS
 VERY LONG. CONDENSATE PIPING SHALL BE INSTALLED AT A
 UNIFORM 1/8 INCH PER FOOT IN ACCORDANCE WITH FBC-M
 307.2.2.
  
 2. PROVIDE THE ACTUAL PRODUCT APPROVAL DOCUMENTATION
 WITH INSTALLATION INSTRUCTIONS ON SITE FOR FIELD
 INSPECTOR TO VERIFY SIZE OF CONDENSING UNIT IS
 COMPATIBLE WITH THE PROPOSED STAND.
  