| Plan Review Notes For Permit 09070433 |
| Permit Number |
09070433 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2009-07-29 14:19:26 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2005 | | | NEC, NFPA-72 2002, NFPA-101 2006, 2004 FBC AS AMENDED, | | | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | COMMENTS REFERENCING SHEETS E1 | | | | | | 1} 13-415.AB.5 INTERIOR LIGHTING POWER, SCOPE. THE | | | INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR A | | | SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING | | | SHALL BE DETERMINED BY THE SPACE-BY-SPACE METHOD | | | DESCRIBED IN SECTION 13-415.B.1. TRADE-OFFS OF INTERIOR | | | LIGHTING POWER ALLOWANCE AMONG PORTIONS OF THE BUILDING | | | FOR WHICH A DIFFERENT METHOD OF CALCULATION HAS BEEN | | | USED ARE NOT PERMITTED. THE INSTALLED INTERIOR LIGHTING | | | POWER IDENTIFIED IN ACCORDANCE WITH SECTION | | | 13-415.AB.5.1 SHALL NOT EXCEED THE INTERIOR LIGHTING | | | POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH | | | SECTION13-415.B.1***THIS CAN BE DEMONSTRATED ON THE | | | PLANS INDICATING THE WATTAGES OF THE LUMINAIRES CHOSEN | | | FOR THE PROJECT CONFORM TO THE DENSITY REQUIREMENTS. | | | INDICATE WATTAGES ON THE FIXTURE SCHEDULE TO CORRELATE | | | WITH THE ONES IN THE CALCULATION. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|