Plan Review Notes
Plan Review Notes For Permit 09070433
Permit Number 09070433
Review Stop B
Sequence Number 1
Notes
Date Text
2009-07-27 11:06:49BUILDING PLAN REVIEW
 PERMIT: 09070433
 ADD: 1731 OLD OKEECHOBEE RD
 CONT: GLOBAL CONSTRUCTION
 TEL: (954)444-8463
  
 FL BLDG CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 SUPPLEMENTS.
  
 PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING
 BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO
 WHAT LEVEL ALTERATION WILL BE COMPLETED UNDERTHIS
 PERMIT.
 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE. THE BUILDING
 STATS SHEET A-0.0 DOES NOT PROVIDE THIS INFORMATION.
  
 2) SHEET A-1.0 INDICATES THE REMOVAL OF THE EXTERIOR
 OVERHEAD DOORS AND NEW STOREFRONT WINDOWS AND DOORS,
 PLEASE PROVIDE THE WIND DESIGN CRITERIA: 1603.1.4 WIND
 DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 2.1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2.2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 2.3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 2.4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
  
 2.5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL.
  
 3) THE PRODUCT APPROVAL NOA 06-1026.08 YKK SERIES
 YHS-50 FS FLUSH GLAZED ALUMINUM STOREFRONT SYSTEM-LMI
 W/ AND W/O STEEL REINFORCEMENT, PLEASE CIRCLE IF THE
 APPROPRIATE BOX FOR MULLIONS FOR MULLION IF THE MULLION
 WILL BE STEEL REINFORCED OR NOT WITH ASSOCIATED
 PRESSURES.
  
 4) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 5) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 5A) PREMANUFACTURED A/C STANDS
  
 5B) PLEASE REVIEW THE MECHANICAL REVIEWERS COMMENTS
 ABOUT A/C EQUIPMENT BEING REQUIRED TO WITHSTAND WIND
 PRESSURE PER MECHCANICAL SECTION: 301.13 FBC
 MECHANICAL. WIND RESISTANCE. MECHANICAL EQUIPMENT,
 APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL
 BE DESIGNED AND INSTALLED TO RESIST WIND PRESSURES ON
 THE EQUIPMENT AND THE SUPPORTS AS DETERMINED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, BUILDING.
 PLEASE PROVIDE DOCUMENTATION ON THE ROOF TOP EQUIPMENT
 .
  
 6) PLANS INDICATE A 1 HR RATED WALL BETWEEN THE
 SHOWROOM AND THE WAREHOUSE AND ALSO BETWEEN THE
 SHOWROOM AND OFFICE AREAS. THERE IS A SECOND SET OF
 DOORS LEADING FROM THE SHOWROOM TO WAREHOUSE WITHOUT
 ANY FIRE RATING, THE DOORS NEXT TO THE MOVED
 TRANSFOREMER. PLEASE SEE REQUIRED OPENING PROTECTIVES
 SECTION 715.3 AND TABLE 715.3.
  
 7) THE ENERGY CALCULATIONS SUBMITTED ARE ON FORM
 400A-2008 WHICH IS THE WHOLE BUILDING METHOD, THIS
 SPACE IS ONLY A PORTION OF THE BUILDING REQUIRING
 METHOD "B" 13-400.0.B
 THE BUILDING ENVELOPE TRADE- OFF METHOD.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  