| 2009-10-19 09:21:14 | BUILDING PLAN REVIEW |
| | PERMIT: 09070394 |
| | ADD: 800 HANDY AVE |
| | CONT: TO BE DETERMINED/ DEAN MOSLEY |
| | TEL: (772)626-6316 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | OCT 19/2009 |
| | |
| | 1-3 COMPLIED. |
| | |
| | 4) TRUSS PACKAGE: |
| | 4A) COMPLIED. |
| | |
| | 4B) ONLY SHINGLES CAN BE APPLIED TO THIS ROOF, WITH A |
| | 7.0 DEAD LOAD THERE IS NO ALLOWANCE FOR A SECOND LAYER |
| | OF SHINGLES WITHOUT THE REMOVAL OF THE FIRST LAYER OR |
| | ROOF TILE. |
| | |
| | 5) 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS |
| | REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE |
| | PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS |
| | SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF |
| | GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE |
| | ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES |
| | POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH |
| | AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS |
| | OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE |
| | TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1. |
| | GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE |
| | SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST. |
| | 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M) |
| | ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL |
| | MISSILE TEST. |
| | |
| | 6) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, |
| | PROVIDE 2 COPIESOF PRODUCT TESTING REPORTS, MISSING |
| | REPORTS ARE AS FOLLOWS: |
| | 9B-72.010(31) |
| | 6A) SINGLE HUNG WINDOWS (B) |
| | |
| | 6B) MULLIONS (B) |
| | |
| | 6C) EXTERIOR SWING DOORS (A) |
| | |
| | 6D) LOUVERS (SOFFITS) (C) |
| | |
| | 6E) SHUTTERS (E) IF LARGE MISSILE IMPACT WINDOWS ARE |
| | NOT INSTALLED |
| | |
| | 6F) ROOFING ASSEMBLIES: SHINGLES |
| | |
| | 7) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| | 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 8) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| | REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITTING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 9) SHEET T-1 INDICATES THE CALCULATIONS FOR EAVE |
| | VENTING BUT NO PROVISIONS ARE PROVIDED FOR THE REQUIRED |
| | 50% OF THE UPPER AIR VENTILATION CLOSER TO THE RIDGE. |
| | R806.2 MINIMUM AREA. THE TOTAL NET FREE VENTILATING |
| | AREA SHALL NOT BE LESS THAN 1/150 OF THE AREA OF THE |
| | SPACE VENTILATED EXCEPT THAT REDUCTION OF THE TOTAL |
| | AREA TO 1/300 IS PERMITTED, PROVIDED THAT AT LEAST 50 |
| | PERCENT AND NOT MORE THAN 80 PERCENT OF THE REQUIRED |
| | VENTILATING AREA IS PROVIDED BY VENTILATORS LOCATED IN |
| | THE UPPER PORTION OF THE SPACE TO BE VENTILATED AT |
| | LEAST 3 FEET (914 MM) ABOVE THE EAVE OR CORNICE VENTS |
| | WITH THE BALANCE OF THE REQUIRED VENTILATION PROVIDED |
| | BY EAVE OR CORNICE VENTS. |
| | |
| | R806.2 MINIMUM AREA. THE TOTAL NET FREE VENTILATING |
| | AREA SHALL NOT BE LESS THAN 1/150 OF THE AREA OF THE |
| | SPACE VENTILATED EXCEPT THAT REDUCTION OF THE TOTAL |
| | AREA TO 1/300 IS PERMITTED, PROVIDED THAT AT LEAST 50 |
| | PERCENT AND NOT MORE THAN 80 PERCENT OF THE REQUIRED |
| | VENTILATING AREA IS PROVIDED BY VENTILATORS LOCATED IN |
| | THE UPPER PORTION OF THE SPACE TO BE VENTILATED AT |
| | LEAST 3 FEET (914 MM) ABOVE THE EAVE OR CORNICE VENTS |
| | WITH THE BALANCE OF THE REQUIRED VENTILATION PROVIDED |
| | BY EAVE OR CORNICE VENTS. |
| | |
| | 10) CONTRACTOR TO BE SIGNED ON BEFORE THE PERMIT CAN BE |
| | ISSUED. FL S S 489. |
| | |
| | SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING FOUR |
| | TIMES THE FEE. |
| | |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | SURVEY: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | |