| 2009-09-20 09:36:51 | ** PROVISO/ REVISION REQUIRED ** |
| | |
| | PLANS ARE REQUIRED TO BE REVISED BEFORE ROUGH |
| | ELECTRICAL INSPECTION. |
| | |
| | |
| | 1) NOTE: ALL EMERGENCY/EXIT LIGHTS SHALL BE CIRCUITED |
| | TO LOCAL LIGHTING BRANCH CIRCUIT PER 700.12F. AS SHOWN |
| | ON PLANS, THE CIRCUITING DOES NOT MEET THE EXCEPTION IN |
| | THE NEC. SHOWN ON A NEW CIRCUIT #5, WHEN THEY ARE |
| | REQUIRED TO BE SPLIT BETWEEN #6 AND #8. |
| | |
| | 2) NOTE: AUTOMATED LIGHTING CONTROLS FOR NEW BEING |
| | INSTALLED IS REQUIRED FOR NEW OFFICE AREA. PLEASE SEE |
| | 13-415.AB.1.1,.1.2. THIS IS A BUILDING BY DEFINITION |
| | GREATER THAN 5K SQ FT. |
| | |
| | 3) NOTE: EXTERIOR LIGHTING CONTROL SHALL MEET |
| | 13-415.AB.1.4. PLANS INDICATE A SINGLE POLE SWITCH |
| | WHICH IS NOT PERMITTED. THE CODE REQUIRES ONE OF THE |
| | METHODS NOTED IN SECTION GIVEN. THIS HAS NOTHING TO DO |
| | WHETHER OR NOT THE BUILDING IS GREATER THAN 5K SQ FT. |
| | |
| | 4) NOTE: PLEASE ACCURATELY SHOW THE ENTIRE ELECTRICAL |
| | SERVICE OF THE BUILDING. SERVICE AS SHOWN IS NOT |
| | ACCURATE FOR ENTIRE SERVICE ON BUILDING. |
| | |
| | 5) NOTE: FIXTURES ON PLANS NEED TO BE SPECIFIC IN ORDER |
| | TO VERIFY 13-415.AB.5. STATING A 2X4 FIXTURE COULD MEAN |
| | THE FIXTURE COULD BE 30VA,32VA, 56VA, 58VA, 60VA, 64VA |
| | OR MORE. THE LPD SHOWN ON PLANS CAN NOT BE CONFIRMED AS |
| | MEETING THE MAXIMUM ALLOWANCES. |
| | |
| | |
| | ** LOW VOLTAGE SYSTEMS, INCLUDING FIRE ALARMS ARE NOT |
| | INCLUDED. SEPARATE PERMITS AS INDICATED ON PLANS |
| | REQUIRED. |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |