| 2009-08-07 12:01:03 | |
| | |
| | ** DENIED REVIEW ** |
| | |
| | 1) NOTE: PLANS ARE ONLY SUBMITTED AS A *PROJECT/PLAN |
| | REVIEW* AND ARE NOT SUBMITTED UNDER PERMIT APPLICATION. |
| | |
| | 2) NOTE: PLEASE SEE THE FOLLOWING CODES WHICH ARE |
| | STATED ON PLANS ARE EITHER NOT ADOPTED OR ARE INCORRECT |
| | EDITIONS.. |
| | |
| | 2007 FLORIDA BUILDING CODE. SHOULD BE 2007 FBC W/2009 |
| | SUPPLEMENTS |
| | |
| | 2007 NFPA-101 ON PLANS: SHOULD BE 2006 NFPA-101. THERE |
| | IS NO 2007 EDITION. |
| | |
| | 2008 NFPA-70 ( NEC) ON PLANS. SHOULD BE 2005 EDITION. |
| | 2008 HAS NOT YET BEEN ADOPTED PER THE STATE OF FLORIDA. |
| | AS PLANS WERE NOT SUBMITTED AS A PERMIT APPLICATION |
| | PLEASE BE AWARE THAT THE 2008 EDITION MAY GO INTO |
| | AFFECT OVER THE NEXT MONTH OR TWO. ** ONLY PERMIT |
| | APPLICATION WITH APPLICABLE FEES PAID WILL *LOCK* PLANS |
| | UNDER SPECIFIC CODES BEFORE THEY ARE REVISED. |
| | |
| | 2007 NFPA-72 ON PLANS: SHOULD BE 2002 NFPA-72. |
| | |
| | ** MOST OF THE ABOVE REFERENCED CODES MAY BE FOUND IN |
| | FLORIDA ADMINISTRATIVE CODE 69A-60.004 AND 69A-3.012 |
| | FOR NFPA ADOPTION DATES. |
| | ** 2007 FBC W/ 2009 REVISIONS REFERENCED CODES CAN BE |
| | FOUND IN CHAPTER 35 OF THE FBC. |
| | |
| | 3) NOTE: PLEASE SUBMIT ELECTRICAL PLANS SHOWING |
| | LOCATIONS OF NEW LIGHTING REQUIRED FOR LIFE SAFETY. |
| | PLEASE SEE FBC 1016 AND NFPA-101 7.8.1.3, 7.9.1.2, |
| | 7.9.2.2. |
| | PLEASE SHOW ALL LIGHTING FIXTURE TYPES AND CONTROLS. |
| | |
| | 4) NOTE: PLEASE SHOW HOW EXTERIOR LIGHTING WILL BE |
| | CONTROLLED PER 13-415.AB.1.4. |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |