Plan Review Notes
Plan Review Notes For Permit 09070377
Permit Number 09070377
Review Stop B
Sequence Number 1
Notes
Date Text
2009-07-30 12:33:41 
 BUILDING PLAN REVIEW
 PERMIT: 09070377
 ADD: 550 S ROSEMARY
 CONT: TO BE DETERMINED
 TEL: (561) 856-6655/ NEYITA
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 SUPPLEMENTS.
  
 PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING
 BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO
 WHAT LEVEL ALTERATION WILL BE COMPLETED UNDERTHIS
 PERMIT.
 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE.
  
 2) 1009.5.3 ENCLOSURES UNDER STAIRWAYS. THE WALLS AND
 SOFFITS WITHIN ENCLOSED USABLE SPACES UNDER ENCLOSED
 AND UNENCLOSED STAIRWAYS SHALL BE PROTECTED BY 1-HOUR
 FIRE-RESISTANCE-RATED CONSTRUCTION OR THE
 FIRE-RESISTANCE RATING OF THE STAIRWAY ENCLOSURE,
 WHICHEVER IS GREATER. ACCESS TO THE ENCLOSED SPACE
 SHALL NOT BE DIRECTLY FROM WITHIN THE STAIR ENCLOSURE.
  
 THERE SHALL BE NO ENCLOSED USABLE SPACE UNDER EXTERIOR
 EXIT STAIRWAYS UNLESS THE SPACE IS COMPLETELY ENCLOSED
 IN 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION. THE OPEN
 SPACE UNDER EXTERIOR STAIRWAYS SHALL NOT BE USED FOR
 ANY PURPOSE.
  
  
 3)FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, PROVIDE
 2 COPIES PRODUCT TESTING REPORTS, MISSING REPORTS ARE
 AS FOLLOWS:
 3A) EXTERIOR SWING DOORS
  
 4) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 5) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6) SHEET A2.1.0 DETAIL# 3 INDICATES THE HANDRAIL AWAY
 FROM THE WALL 2 1/2". BOTH WITHIN THE BUILDING CODE
 1012.6 AND 11-4.9.4(3) INDICATE TTHE HANDRAILS ARE TO
 BE SET NO MORE THAN
 1 1/2 INCHES, THE NFPA 101 SECTION 7.2.2.4.4.5 STATES 2
 1/4 INCHES AWAY.
  
 7) SHEET S-1 DOES NOT INDICATE THE MINIMUM DISTRIBUTED
 LIVE LOADS, TABLE 1607.1.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.