Plan Review Notes
Plan Review Notes For Permit 09070347
Permit Number 09070347
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2009-07-27 13:03:31UPGRADE FIRE ALARM SYSTEM
  
 1. THE PERMIT APPLICATION INDICATES A VALUE OF $
 259,000 DOLLARS. PLEASE PROVIDE A COPY OF THE CONTRACT
 REPRESENTING THE COST OF LABOR AND PARTS TO PERFORM
 THIS WORK.
  
 2. PLEASE PROVIDE INFORMATION ON THE C I CABLE THAT IS
 PLANNED TO BE USED TO MEET THE SURVIVABILITY
 REQUIREMENTS.
  
 3. A GENERAL DISCUSSION NEEDS TO OCCUR REGARDING IT,
 STORAGE, RESTROOMS, ELECTRICAL, AND LARGE CONFERENCE
 ROOMS. IN SOME LOCATIONS NO DEVICES ARE SHOWN ON THE
 PLANS. ARE SOME OF THE STORAGE AREAS DISPLAYED ON THE
 PLANS THAT ARE ABSENT OF DEVICES PAPER CLOSETS. PLEASE
 PROVIDE RATIONALE FOR MISSING DEVICES.
  
 4. PLEASE INDICATE ON THE PLANS WHAT THE VOICE
 EVACUATION MESSAGE IS EXPECTED TO ADVISE PERSONS IN THE
 BUILDING.
  
 5. SIGNALING APPLIANCES MISSING FROM MENS AND WOMENS
 RESTROOM NEAR STAIR # 3 ON PAGE FA-02.
  
 6. CORRIDOR BELOW SECURITY DESK APPEAR TO CONTAIN
 INSUFFICIENT SIGNALING APPLIANCES ON PAGE FA-03.
  
 7. THERE DOES NOT APPEAR TO BE ENOUGH SIGNALING
 APPLIANCES ON PAGE FA-05.
  
 8. ON PAGE FA-06 NO INITIATING DEVICES SHOWN AT TOP OF
 THE ATRIUM. IS THIS CORRECT.
  
 9. NO MANUAL PULL STATIONS SHOWN IN PARKING GARAGE. IS
 THIS CORRECT.
  
 10. PLEASE INDICATE ON THE DRAWINGS THE SEQUENCE FOR
 REPLACING FIRE ALARM EQUIPMENT AND STILL BE ABLE TO
 PROVIDE FIRE ALARM COVERAGE FOR THE BUILDING.
  
 11. WHAT EXISTING DEVICES ARE PRESENT IN THE
 CONDOMINIUMS.
  
 12. THE NEW FIRE ALARM SYSTEM WHEN COMPLETED SHALL BE
 MONITORED BY A UL LISTED CENTRAL STATION APPROVED FOR
 CENTRAL STATION SERVICE.
  
 13. WHEN SYSTEM IS COMPLETED, SYSTEM IS TO BE TESTED
 AND APPROVED BY CITY OFFICIALS.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE