| 2009-08-05 16:37:06 | DENIED |
| | REFERENCE: |
| | FBC-2007 W/2009 SUPPLEMENTS |
| | FBC-2007 PLUMBING |
| | FBC-2007 CHAPTER 11 |
| | |
| | 1. PER TABLE 403.1 A DRINKING FOUNTAIN IS REQUIRED. |
| | INDICATE LOCATION ON THE FLOOR PLAN. |
| | |
| | 2. SHT P-1 TITLE BLOCK INDICATES SUITE 104-B WHERE AS |
| | THE APPLICATION AND SYSTEM INDICATE THE SUITE NUMBER AS |
| | 205. ALSO THE FLOOR PLAN DOES NOT REFLECT THE FLOOR |
| | PLAN SHOWN ON THE ARCHITECTURAL SHEETS. PLEASE |
| | CORRELATE. SECTION 106.1.1. |
| | |
| | 3. SHT A-1 FLOOR PLAN. SHOW THE CLEAR FLOOR SPACE AND |
| | TURNING AREA REQUIRED BY SECTIONS 11-4.16.2, 11-4.19.3 |
| | & 11-4.22.3. IT APPEARS THAT THE DOOR MAY SWING INTO |
| | THE CLEAR FLOOR SPACE OF THE W/C. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |