| Date |
Text |
| 2009-07-24 19:21:51 | |
| | ** DENIED ** |
| | |
| | 1) NOTE: PLEASE COORDINATE ALL PLANS SUBMITTED. PLEASE |
| | SEE THAT TWO SET OF PLANS SUBMITTED CONTAIN ELECTRICAL |
| | AND PLUMBING PLANS FROM TWO DIFFERENT SUITES OR UNITS. |
| | FOR EXAMPLE ONE SET CONTAINS ELECTRICAL SHEETS FOR UNIT |
| | 104-B AND THE OTHER FOR SUITE 205. |
| | AS THE PERMIT APPLICATION IS APPLYING FOR WORK IN UNIT |
| | 205 THE ELECTRICAL REVIEW WILL BE DONE FOR 205. |
| | |
| | |
| | 2) NOTE: PLEASE SEE THAT THE SUBMITTED WHOLE BUILDING |
| | METHOD A CALCULATIONS MAY NOT BE USED. THIS IS A TENANT |
| | BUILDING OUT AND NOT A WHOLE BUILDING BY THE |
| | DEFINITIONS SET FORTH IN CHAPTER 13 SECTION 202 OR |
| | CHAPTER 2 OF THE FBC. |
| | PLEASE SEE 13-415.AB.5. |
| | THE PLANS SUBMITTED ALSO CONTAIN LIGHTING CALCULATIONS |
| | PER SECTIONS STATED FROM THE 2004 FBC. . |
| | IT IS ALSO NOT PERMISSIBLE TO USE TWO DIFFERENT METHODS |
| | OF CALCULATIONS. |
| | PLEASE SEE TABLE ON SHEETS AS HALL AREA STATES A |
| | WATTAGE TOTAL OF 116 YET BASED ON THE WATTAGE OF THE |
| | FIXTURES ON THE IDR OF THE SUBMITTED ENERGY |
| | CALCULATIONS THIS IS NOT POSSIBLE. THE IDR STATES 2-64 |
| | WATT FIXTURES WHICH WOULD BE 128WATTS AND NOT THE 116 |
| | AS STATED ON PLANS. THIS WOULD NOT COORDINATE WITH THE |
| | FIXTURES NOTES. |
| | PLEASE SEE OTHER ROOMS AND AREAS AND THE ALLOWANCES |
| | UNDER THE 2007 FBC WITH THE 2009 REVISIONS. |
| | THE IDR ALSO INDICATES MANUAL ON/OFF WHICH IS NOT WHAT |
| | IS ON PLANS. |
| | |
| | 3) NOTE: THE PLANS STATE THE 2007 FBC HOWEVER AS |
| | ADOPTED THE 2007 FBC WITH THE 2009 REVISIONS HAS |
| | SUBSTANTIAL CHANGES OVER THE 2007 FBC. |
| | |
| | *** AS PLANS ARE NO LONGER RELEASED TO CONTRACTOR PER |
| | THE NEW BUILDING DIRECTOR, ONCE CORRECTIONS ARE MADE |
| | INSERTION OF NEW SHEETS AND DOCUMENTS WILL NEED TO TAKE |
| | PLACE IN THIS DEPARTMENT. |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |