Plan Review Notes
Plan Review Notes For Permit 09070291
Permit Number 09070291
Review Stop E
Sequence Number 1
Notes
Date Text
2009-07-29 10:14:44 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 ALL COMMENTS RELATE TO SHEET A-5, UNLESS OTHERWISE
 NOTED.. ALL CODE ARTICLES REFERENCED ARE 2005 NEC
 UNLESS OTHERWISE NOTED.
  
 1} THE AHU AND CU # 2 & 3 RATING AND OCP SIZES DO NOT
 CORRELATE WITH THE MECHANICAL SHEETS SUBMITTED
  
 2} 210.11(C)(3) BATHROOM BRANCH CIRCUITS IN ADDITION TO
 THE NUMBER OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS
 OF THIS SECTION, AT LEAST ONE 20-AMPERE BRANCH CIRCUIT
 SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE
 OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER
 OUTLETS.*** NO BATH CIRCUITS ARE LISTD ON THE PANEL
 SCHEDULES.
  
 3} THE DISCONNECT LOCATION FOR THE CONDENSERS AND WINE
 ROOM CHILLER ARE IN VIOLATION OF 110.26 CLEARANCE
 REQUIREMENTS AS DRAWN.
  
 4} THE COUNTERTOP RECEPTACLE NEXT TO THE DOUBLE OVEN
 MUST BE GFI PROTECTED PER210.8(A)(6).
  
 5} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1)***
 ONE IS REQUIRED ON THE EAST WALL OF THE BREAKFAST ROOM
 TO COMPLY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  