| Notes |
| Date |
Text |
| 2009-07-29 10:14:44 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009 | | | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND | | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | ALL COMMENTS RELATE TO SHEET A-5, UNLESS OTHERWISE | | | NOTED.. ALL CODE ARTICLES REFERENCED ARE 2005 NEC | | | UNLESS OTHERWISE NOTED. | | | | | | 1} THE AHU AND CU # 2 & 3 RATING AND OCP SIZES DO NOT | | | CORRELATE WITH THE MECHANICAL SHEETS SUBMITTED | | | | | | 2} 210.11(C)(3) BATHROOM BRANCH CIRCUITS IN ADDITION TO | | | THE NUMBER OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS | | | OF THIS SECTION, AT LEAST ONE 20-AMPERE BRANCH CIRCUIT | | | SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE | | | OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER | | | OUTLETS.*** NO BATH CIRCUITS ARE LISTD ON THE PANEL | | | SCHEDULES. | | | | | | 3} THE DISCONNECT LOCATION FOR THE CONDENSERS AND WINE | | | ROOM CHILLER ARE IN VIOLATION OF 110.26 CLEARANCE | | | REQUIREMENTS AS DRAWN. | | | | | | 4} THE COUNTERTOP RECEPTACLE NEXT TO THE DOUBLE OVEN | | | MUST BE GFI PROTECTED PER210.8(A)(6). | | | | | | 5} RECEPTACLE SPACING MUST COMPLY WITH 210.52(A)(1)*** | | | ONE IS REQUIRED ON THE EAST WALL OF THE BREAKFAST ROOM | | | TO COMPLY. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|